10. Concealed Floor-Standing Type (FM Type)
10-3. Other component specifications
MODEL NO.
Indoor Unit
Power Transformer
Rated
Primary
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil sensor)
Coil resistance
Thermistor (Room or coil sensor)
Coil resistance
Solenoid control valve or coil
Solenoid control valve
Solenoid coil
ECO MULTI SYSTEM Unit Specifications
SPW-FM93 ~ 253GH56
V, Hz
Ω
WHT –WHT : 110
RED – RED : 2.3
˚C
PBC-41E-S25 , PBC-41E-S35
-10 ˚C : 23.7 ± 5 %
KΩ
-5 ˚C : 18.8 ± 5 %
0 ˚C : 15.0 ± 5 %
5 ˚C : 12.1 ± 5 %
10 ˚C : 9.7 ± 5 %
0 ˚C : 16.5 ± 5 %
KΩ
5 ˚C : 12.8 ± 5 %
10 ˚C : 10.0 ± 5 %
20 ˚C : 6.3 ± 5 %
30 ˚C : 4.0 ± 5 %
IKV-24D12 (SPW-FM93 ~ 253GH56)
DKV-MOZS550E0 (SPW-FM93 ~ 253GH56)
I - 127
ATR-II215TB
AC 230 V, 50 Hz
10.2 V 1.4 A
14 V 0.5 A
,
BRN – BRN : 0.5
145
20 ˚C : 6.5 ± 5 %
,
30 ˚C : 4.4 ± 5 %
,
40 ˚C : 3.1 ± 5 %
,
45 ˚C : 2.6 ± 5 %
,
KTEC-35-S6
40 ˚C : 2.7 ± 5 %
,
45 ˚C : 2.2 ± 5 %
,
50 ˚C : 1.8 ± 5 %
,
55 ˚C : 1.5 ± 5 %
,
1
SM830052