Sanyo SPW-C483GYH8 Service Manual page 133

Eco multi system
Table of Contents

Advertisement

10. Concealed Floor-Standing Type (FM Type)
10-3. Other component specifications
MODEL NO.
Indoor Unit
Power Transformer
Rated
Primary
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil sensor)
Coil resistance
Thermistor (Room or coil sensor)
Coil resistance
Solenoid control valve or coil
Solenoid control valve
Solenoid coil
ECO MULTI SYSTEM Unit Specifications
SPW-FM93 ~ 253GH56
V, Hz
WHT –WHT : 110
RED – RED : 2.3
˚C
PBC-41E-S25 , PBC-41E-S35
-10 ˚C : 23.7 ± 5 %
KΩ
-5 ˚C : 18.8 ± 5 %
0 ˚C : 15.0 ± 5 %
5 ˚C : 12.1 ± 5 %
10 ˚C : 9.7 ± 5 %
0 ˚C : 16.5 ± 5 %
KΩ
5 ˚C : 12.8 ± 5 %
10 ˚C : 10.0 ± 5 %
20 ˚C : 6.3 ± 5 %
30 ˚C : 4.0 ± 5 %
IKV-24D12 (SPW-FM93 ~ 253GH56)
DKV-MOZS550E0 (SPW-FM93 ~ 253GH56)
I - 127
ATR-II215TB
AC 230 V, 50 Hz
10.2 V 1.4 A
14 V 0.5 A
,
BRN – BRN : 0.5
145
20 ˚C : 6.5 ± 5 %
,
30 ˚C : 4.4 ± 5 %
,
40 ˚C : 3.1 ± 5 %
,
45 ˚C : 2.6 ± 5 %
,
KTEC-35-S6
40 ˚C : 2.7 ± 5 %
,
45 ˚C : 2.2 ± 5 %
,
50 ˚C : 1.8 ± 5 %
,
55 ˚C : 1.5 ± 5 %
,
1
SM830052

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents