Sounder (Siren) Connections - Honeywell Ademco Vista-12D Installation And Setup Manual

Table of Contents

Advertisement

Installation and Setup Guide
Wiring Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)
TOTAL CURRENT DRAIN OF ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Wire
Size
50 mA or less
0.6mm O.D.
152m
0.8mm O.D.
228.6m
1mm O.D.
396m
1.2mm O.D.
457m
* Includes Keypads, RF Receivers, Zone Expander/Relay Units, or TeleCommand Phone Module.
Maximum wire lengths for any device that is wired directly to the control can also be determined from the Wiring Run
Chart, based on the current drain of that device alone.
The length of all wire runs for all partitions combined must not exceed 457m when unshielded quad conductor cable
is used (228m if shielded/screened cable is used). This restriction is due to the capacitive effect on the data lines
when quad cable is used.

Sounder (Siren) Connections

1. Make sounder connections to alarm output terminals 3
(+) and 4 (–).
For supervised output, continue with steps 2 and 3.
2. Cut the red Siren Supervision Jumper located above
terminals 2 and 3 on the control board.
3. Connect a 2k ohm resistor across the terminals of the
last sounder.
TERMINALS ON
CONTROL BOARD
_
4
ALARM
OUTPUT
TERMINALS
+
3
2
CUT RED JUMPER ON CONTROL
BOARD TO ENABLE SIREN
(SOUNDER) SUPERVISION.
Figure 4. Sounder Wiring (Supervised)
2-4
100 mA
76m
116m
198m
305m
EXTERNAL ALARM
SOUNDER
_
2000
OHM
OBSERVE
EOL
POLARITY
+
RESISTOR
IF SIREN SUPERVISION IS ENABLED
(RED JUMPER ON CONTROL BOARD IS CUT)
CONNECT A 2000 OHM RESISTOR ACROSS
THE EXTERNAL SOUNDER AS SHOWN BY
THE DOTTED LINE.
DO NOT CONNECT THE RESISTOR AT THE
ALARM OUTPUT TERMINALS THEMSELVES!
300 mA
500 mA
24m
15m
40m
24m
67m
40m
100m
70m
Notes
• The 12VDC sounder output activates
when an alarm occurs.
• Total current drain from this output
cannot exceed 2 amps (going beyond 2
amps will overload the power supply,
or may cause the electronic circuit
protecting the sounder output to
activate).
• You must install a battery, since the
battery supplies this current.
• Do NOT perform steps 2 and 3 if using
a self-activated siren.
600 mA
13m
20m
35m
52m

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents