Sounder (Bell) Connections; Basic Connections; Supervised Output; Connecting The Keypads And Other Addressable Devices - Honeywell ADEMCO VISTA SERIES VISTA-21iP Installation And Setup Manual

Hide thumbs Also See for ADEMCO VISTA SERIES VISTA-21iP:
Table of Contents

Advertisement

Installation and Setup Guide

Sounder (Bell) Connections

Basic Connections

3
4
ALARM OUTPUT
10.5 - 13.5 VDC
2A MAX.

Connecting the Keypads and Other Addressable Devices

Connections

4 _
5 +
6 IN
7 OUT
Supplementary Power
(optional)
U L
Use a UL Listed,
battery-backed supply for
UL installations. The battery
supplies power to these
keypads in case of AC
power loss.
The battery-backed power
supply should have enough
power to supply the
keypads with the UL
required minimum standby
power time.
2-4
1. Make sounder connections to alarm output terminals 3 (+) and 4 (–).
2. If not using bell supervision, connect the supplied 820 ohm resistor across terminals 3
and 4. If using bell supervision, see Supervised Output paragraph below.
• The 12VDC sounder output activates when an alarm occurs.
• Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will
overload the power supply, or may cause the electronic circuit protecting the sounder
output to trip).
• You must install a battery, since the battery supplies this current.

Supervised Output

1. Connect the supplied 820 ohm Bell Supervision EOL resistor across the terminals of the
last sounder. See Figure 5.
Bell Supervision Note: The value of the Bell Supervision EOL Resistor is 820 ohms.
High Impedance Device Note: If a high impedance sounding device is used (ex.
745X3), the bell supervision resistor (included) must be installed at the device.
2. Set field ∗91 Option Selection for Bell Supervision (option 1).
This control complies with NFPA requirements for temporal pulse sounding of fire notification
appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses –
pause – 3 pulses–etc..
U L
• Use only UL Listed sounding devices for
UL installations.
• Bell supervision is required for fire alarm
installations.
• The total current drawn from the alarm
output and the auxiliary power output,
combined, cannot exceed 600 mA. In
addition, the sounding device must be a
UL Listed audible signal appliance rated
to operate in a 10.2-13.8 VDC voltage
range, and must be mounted indoors.
Connect keypads and other addressable devices (4204, 4219, 4229, 4286, 5881, etc.) to
the control's keypad terminals as shown on the Summary of Connections diagram. The
system supports up to 8 keypads, which can be assigned to partitions in any
combination (see program fields *190-*196).
Use the Table of Device Addresses to determine the appropriate address for each device.
Determine wire size using the Wire Run Chart on the following page. For single 4-wire
runs, determine the current drawn by all units, then refer to the Wiring Run chart to
determine the maximum length that can be safely used for each wire size.
Use supplementary power if the
control's aux. power load for all
devices exceeds 600mA (suggested
power supply: AD12612). Connect
as shown in Figure 6. Be sure to
connect the negative (–) terminal
on the power supply unit to
terminal 4 (AUX –) on the control.
IMPORTANT: Keypads powered
from supplies that do not have a
backup battery will not function if
AC power is lost. Make sure to
power at least one keypad in each
partition from the control's
auxiliary power output.
TERMINALS ON
CONTROL BOARD
4
ALARM
OUTPUT
TERMINALS
3
2
IF BELL SUPERVISION IS ENABLED
( 91 ENABLED)
CONNECT AN 820 OHM RESISTOR ACROSS
THE EXTERNAL SOUNDER AS SHOWN BY
THE DOTTED LINE.
DO NOT CONNECT THE RESISTOR DIRECTLY
TO THE ALARM OUTPUT TERMINALS!
Figure 5. Sounder Wiring (Supervised)
SUPPLEMENTARY
CONTROL TERMINAL STRIP
POWER SUPPLY
+
IMPORTANT:
MAKE THESE
CONNECTIONS
DIRECTLY TO
SCREW
TERMINALS AS
SHOWN.
Figure 6. Using a Supplementary Power Supply
EXTERNAL ALARM
SOUNDER
_
820
OBSERVE
OHM
POLARITY
EOL
+
RESISTOR
AUX. AUX. DATA
DATA
+
IN
OUT
4
5
6
7