Honeywell Ademco Vista-12D Installation And Setup Manual page 44

Table of Contents

Advertisement

Installation and Setup Guide
FIELD
TITLE and DATA ENTRIES
Low Battery Report Code
*63
0 = disable; 1-F = see description above ∗59
Test Report Code
*64
0 = disable; 1-F = see description above ∗59
Open Report Code
*65
0 = disable; 1-F = see description above ∗59
Arm Away/Stay Report Code
*66
0 = disable; 1-F = see description above ∗59
RF Low Battery Report Code
*67
0 = disable; 1-F = see description above ∗59
Cancel Report Code
*68
0 = disable; 1-F = see description above ∗59
Alarm Restores
*69
Send restore code (if fault cleared):
0 = at siren timeout (if restored) or at disarm
(whether restored or not)
1 = dynamically as the fault clears
2 = only after a disarm
Alarm Restore Report Code
*70
0 = disable; 1-F = see description above ∗59
Trouble Restore Report Code
*71
0 = disable; 1-F = see description above ∗59
Bypass Restore Report Code
*72
0 = disable; 1-F = see description above ∗59
AC Mains Restore Report Code
*73
0 = disable; 1-F = see description above ∗59
Low Battery Restore Report Code
*74
0 = disable; 1-F = see description above ∗59
RF Low Battery Restore Code
*75
0 = disable; 1-F = see description above ∗59
Test Restore Report Code
*76
0 = disable; 1-F = see description above ∗59
4-8
EXPLANATION
Sent when a low-battery condition exists in the
system's battery.
Sent periodically to test that the communicator and
phone lines are operational. Frequency of report is set in
Scheduling mode (event 11).
Sent upon disarming of the system in the selected
partitions.
This option allows for independent programming of
Away and Stay reports for each partition.
NOTE: "OPEN" reports are not sent if the associated
closing report is not enabled.
Sent when a wireless transmitter low-battery condition
exists.
Sent upon disarming of the system after an alarm
condition was reported.
Alarm restore message will be sent upon condition
selected.
Sent when an alarm zone is restored to its non-faulted
condition or at the times selected in field *69.
Sent when a trouble in a zone is restored
Sent when a zone that has been bypassed is
unbypassed, either manually or when the
partition/system is disarmed.
Sent when AC mains has been restored after an AC
mains outage.
Sent when a system low-battery condition is restored
to normal.
Sent when a transmitter's low battery condition is
restored (i.e., new battery installed).
Sent when the Test mode is exited.

Hide quick links: