System Status Report Codes

Zone report codes are programmed using interactive ✱ 56 or ✱ 58 Zone Programming modes, while
system status (non-alarm) codes and restore codes are entered in the following data fields. The actual
report code digits that you enter depend upon the particular installation, and should agree with the
Central Station office receiving the signals.
To disable a report code, enter "0" in the first entry.
3+1, 4+1 Standard or Robofon 8 Format: Enter a code in the first entry: 1–9, A, B, C, D, E, or F.
Enter #+10 for A (this reports a "0" on some receivers), #+11 for B, #+12 for C, #+13 for D, #+14 for E,
#+15 for F.
Entering 0 in the second box advances to the next field.
Expanded or 4+2 Format: Enter codes in both entries (first and second digits) for 1–9 or A–F, as
described above. An entry of "0" in the second entry eliminates the expanded message for that report.
ADEMCO or Robofon Contact ID® Reporting: Enter a digit in the first entry to enable the zone to
report. Use a different digit for each zone until you have used up available digits. If the number of zones
exceeds the number of available digits, begin with digit 1 again. This is an "enabling" code only and is
not the actual code sent to the Central Station office. Entries in the second entry pair are ignored. An
entry of 0 in the first box disables the report.
FIELD
TITLE and DATA ENTRIES
Exit Error Report Code
*59
0 = no report
1-F = report code; see description above
Trouble Report Code
*60
0 = disable; 1-F = see description above ∗59
Bypass Report Code
*61
0 = disable; 1-F = see description above ∗59
AC Mains Loss Report Code
*62
0 = disable; 1-F = see description above ∗59
Data Field Programming
EXPLANATION
After arming the system, zones remaining open after
exit delay expires cause an alarm sound at the keypad
and external sounder (keypad also displays "EXIT
ALARM"), and entry delay begins. Disarming before the
end of the entry delay stops the alarm sounding and no
message is sent to the central station. The keypad will
display "CA" (fixed-word) or "CANCELED ALARM"
(alpha display).
If the system is not disarmed before entry delay
expires, an "EXIT ALARM" message will be sent to the
central station if Exit Error Report Code is enabled.
The keypad will display "EA" (fixed-word ) or "EXIT
ALARM" (alpha display), and alarm sounding
continues until the system is disarmed (or timeout
occurs).
An Exit Alarm condition will also result if a fault
occurs in an exit or interior zone within 2 minutes
following the end of the exit delay, and an "EXIT
ALARM" message will be sent to the central station
With Contact ID format, the message will contain the
zone number and error code 374 ("ALARM–EXIT
ERROR").
Sent if a zone has a trouble condition.
Sent when a zone is manually bypassed or is
automatically bypassed at the end of exit delay.
Timing of this report is random with up to a 1-hour
delay. If AC mains restores before the report goes out,
there is no "AC RESTORE" report.
4-7