Bc10 Display Codes - Buderus Logamax plus Installation Instructions Manual

Gb162-80 kw/100 kw condensing gas boiler
Hide thumbs Also See for Logamax plus:
Table of Contents

Advertisement

13
Display information

13.5 BC10 Display codes

The folllowing table contains all codes that can show on the BC10 display. To show the current display code and/or
e
subcode, press the
-key repeatedly. There are 3 main code groups:
Operating codes - this code gives the status of the boiler.
No action is necessary.
Locking faults - the boiler resumes normal operation
when the fault has cleared.
Blocking faults - the boiler is locked and will only restart
after a manual reset. The pump will operate continuously
for frost protection.
If a blinking code is displayed together with other codes, all displayed codes will blink.
A locking code will always show on the first screen of the BC10.
Main
Sub-
display
display
code
code
Operating phase:
[\/-/\|
Communication test while starting up. This display code flashes five
times within 5 seconds while starting up to indicate that the communica-
tion between the UBA 3 and the BC10 basic controller is being tested. If
a new UBA 3 or a new KIM was fitted, this code will flash for max.
10 seconds.
Blocking fault:
[\/-/\|
If this code continues to flash on the display, there is a fault in the com-
munication between the UBA 3 and the BC10 basic controller.
Any display code with a dot in bottom right hand corner.
[-/a/\]
[2/0/8|
Operating phase:
1)
The boiler is in flue gas test or service mode.
[-/h/\|
[2/0/0|
Operating phase:
The boiler is in heating mode.
1)
Any display code with a blinking dot in bottom right hand corner.
[-/h/}
[2/0/0|
Operating phase:
1)
The boiler is in manual operation mode.
[=/h/\|
[2/0/1|
Operating phase:
The boiler is in DHW mode.
1)
Operating phase:
[=/h/\|
[2/0/1|
Pump run-over time via the external hot water cylinder 130 seconds at
1)
minimum speed.
The LED "Burner operation" is off.
Operating phase:
[0/a/\|
[2/0/2|
The switch optimization program is activated.
1)
This program is activated if there has been a DHW request from an RC
regulator more frequently than once every 10 minutes. This means that
the boiler cannot be restarted until at least ten minutes have elapsed
since initial burner start-up.
Table 19 BC10 Display codes
1)
Only visible on the Service Tool or a specific RC controller.
74
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
Display codes
Key to display code
Other effects
No heating operation and no DHW.
The room temperature is too high.
The room temperature is not possibly
reached.