Buderus Logamax plus Installation Instructions Manual page 67

Gb162-80 kw/100 kw condensing gas boiler
Hide thumbs Also See for Logamax plus:
Table of Contents

Advertisement

Pull the air suction tube from the fan (fig. 82).
Carefully open the 4 snap retaining clips on the burner
cover (fig. 83). The retaining clips may be under tension.
Remove the retaining clips.
Remove the burner cover with the gas/air unit (fig. 84).
12.3.3 Remove the burner and the burner seal
Remove the burner seal (fig. 85, pos. 1) and replace it if
necessary.
Remove the burner plate (fig. 85, pos. 2) and clean it on
all sides using compressed air or a soft brush.
When re-installing the burner plate make sure that the notch
is on the right-hand side (fig. 85, see detailed picture).
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
Fig. 82 Pulling the air suction tube from the fan
Fig. 83 Opening the retaining clips
Fig. 84 Removing the burner cover with the gas/air unit
1
2
Fig. 85 Removing the burner plate and the burner seal