Open the screw plug on the testing nipple for the gas inlet
pressure by 2 turns (fig. 57, pos. 1).
Reset the digital pressure gauge to "0".
NOTICE
Throughout the measuring operation, keep the
digital pressure gauge in the same position
(horizontal or vertical) in which it was reset
to "0".
Connect the pressure gauge connection tube to the posi-
tive port of the testing nipple (fig. 57, pos. 2).
Slowly open the gas valve by pushing on the gas valve
and turning it ¼ rotation in an counterclockwise direction
(fig. 54, page 49). The gas valve is open when it is in the
vertical position.
Switch ON the heating system by pressing the main
switch of the BC10 basic controller (fig. 58, pos. 1).
Press and hold the "Chimney sweep" button (fig. 58,
pos. 3) (approx. two seconds), until the dot in the right-
hand bottom corner of the display (fig. 58, pos. 9)
appears. See also table 8, "Flue gas test", page 41.
After the LED "Burner operation" (fig. 58, pos. 6) has lit
up wait for one minute until the boiler is burning at full
load.
Measure the gas supply pressure and enter it in the start-
up report, page 85.
The gas supply pressure must be:
– for natural gas min. 7 inch W.C. (17.4 mbar),
max. 10.5 inch W.C. (26.1 mbar), nominal supply pres-
sure 8 inch W.C. (19.9 mbar).
– for LPG min. 8 inch W.C. (19.9 mbar),
max. 13 inch W.C. (32.3 mbar), nominal supply pres-
sure 11 inch W.C. (27.4 mbar).
Press the "Service" button (fig. 58, pos. 4) repeatedly
until the temperature reading is shown in the display.
Press the "Chimney sweep" button (fig. 58, pos. 3) to
clear the reading. Also see table 8, "Flue gas test",
page 41
WARNING
A leaking testing nipple causes explosive
fumes.
Check the testing nipples used for leaks.
Only use approved detection products to
locate leaks.
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
1
2
Fig. 57 Measuring the gas supply pressure
10
110
100
120
888
130
90
140
11
1
1
Fig. 58 BC10 basic controller
pos. 1:
Main switch
pos. 2:
"Reset" button
pos. 3:
"Chimney sweep" button
pos. 4:
"Service" button
pos. 5:
Connection possibility for the diagnosis connector
pos. 6:
LED "Burner operation"
pos. 7:
LED "Central heat demand"
pos. 8:
Space heating water temperature knob
pos. 9:
Display
pos. 10: DHW temperature knob
pos. 11: LED "DHW demand"
Start-up procedure
9
8
130
110
150
90
170
190
2
3
4
5
6
9
7
51