12.3.5 Disconnect the condensate trap
Disconnect the condensate trap hose (fig. 89, pos. 3)
and the rubber sleeve (fig. 89, pos. 2) from the conden-
sate trap (fig. 89, pos. 1).
Turn the condensate trap a quarter rotation counter-
clockwise (fig. 89).
Disconnect the condensate trap from the coupling and
remove it (fig. 90, pos. 1).
Rinse the condensate trap to clean it.
Fill the condensate trap with water and reinstall it.
NOTICE
The condensate trap has a bayonet connector.
After inserting it, the condensate trap must be
turned ¼ rotation clockwise to click into posi-
tion.
12.3.6 Remove the condensate collector
Disconnect the flexible condensate drain hose and bend
it backwards (fig. 91).
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!
1
Fig. 89 Disconnecting the condensate trap hose
pos. 1:
Condensate trap
pos. 2:
Rubber sleeve
pos. 3:
Condensate trap hose
1
Fig. 90 Disconnecting the condensate trap
Fig. 91 Removing the condensate trap hose