Section Ii: Masonry Insert Installation - New Buck Corporation 74 Manual

Non-catalytic unit
Hide thumbs Also See for 74:
Table of Contents

Advertisement

The Model 74 may be installed using an all masonry fireplace built in accordance with the
Uniform Building Code and National Fire Protection Association (NFPA). The first step in
this type of installation is to determine the acceptability of the fireplace and chimney for use
with a woodstove. Both the construction and condition of the fireplace are important consid-
erations when installing a woodstove. The chimney should extend at least 3' above the roof
and at least 2' above any point of the roof within 10'.
REMEMBER TO HAVE YOUR CHIMNEY INSPECTED FOR LEAKS AND BLOCKAGE
BEFORE YOU INSTALL YOUR STOVE. "DO NOT CONNECT THIS UNIT TO A
CHIMNEY FLUE SERVING ANOTHER APPLIANCE."
MINIMUM CLEARANCE MASONRY INSERT
MODEL 74
A. Side Wall Combustible
B. Front Floor Protector
C. Side Floor Protector
D. Side Wood Trim
E. Top Wood Trim
F. Mantel or Brackets
1. The hearth must be of masonry construction and must extend a minimum of 20" in front of
the firebox opening and a minimum of 8" to either side of the firebox opening.
2. If there is not minimum hearth protection from the front of the firebox opening and the
front of the masonry hearth, a floor protector must be used in front of the hearth to
protect combustible materials. The floor protector must be 3/8" minimum thickness non-
combustible material or equivalent.(See Page 12,13.)
SECTION II
MASONRY INSERT INSTALLATION
CAUTION
16"
20"
8"
10"
10"
24"
Page 4
E
C
A
F
D
B

Advertisement

Table of Contents
loading

Table of Contents