INSTALLATION PRECAUTIONS
The following precautions are mandatory for a safe installation.
(A) Compliance with local building codes and regulations is mandatory.
(B) Be careful not to damage the unit in handling and unpacking component parts and accessories.
(C) Model 51zc Cabinet, use only 6"listed 2100º UL 103 HT TYPE Chimney with the 51zc
Cabinet (ONLY AFTER) one of the follwing new Buck Corparation Stoves 51, T-51, 74, T-74,
has been installed into the 51ZC Cabinet.
(D) he chimney must extend a minimum of three feet (3') above the highest point where it penetrates the
roof (three feet (3') above a flat roof or up to a 2 /12 pitch roof ), and the chimney must extend a
minimum of two feet (2') higher than any portion of the building within ten feet (10') of the chim-
ney. The minimum height is fourteen feet (14'). The maximum height is thirty feet (30'). A two-inch
(2") clearance must be maintained between the chimney and any combustible materials at all points.
(E) A rain cap must be used to terminate the chimney to prevent down-draft. Use the factory approved
rain cap which is approved for the type chimney being installed.
(F) "DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER
APPLIANCE." DO NOT USE A FLUE INTENDED FOR A GAS APPLIANCE."DO
NOT CONNECT TO ANY DISTRIBUTION DUCT OR SYSTEM."