Fireplace Placement Requirements
•
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
•
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
•
Fireplace should be located out of traffic and away from furniture and draperies.
•
Fireplace must be placed so the gaps below and above the glass frame do not become blocked.
•
Fireplace may be placed in a bedroom. Please be aware of the large amount of heat this appliance produces
when determining a location.
Clearances
(a) Clearance to Side of Fireplace 5/8" (16mm). Do not place insulation in this space.
NOTE: Drywall or other combustible may contact the side of the fireplace in front of the framing. The
material must not protrude in front of the fireplace and may be a maximum ½" (13mm) thick.
(b) Clearance to Back of Fireplace 1/8" (4mm). Do not place insulation in this space.
(c) When installed, walls in front of the fireplace must be a minimum 3" (77mm) to the side of the fireplace.
b
a
c
Raised Fireplaces
•
The fireplace (and hearth, if desired) may be placed on a platform designed to support the fireplace and vent.
•
The base of the fireplace must be a minimum 60" below the room ceiling.
The firebox opening is approximately 10.375" (264mm) above the base of the fireplace. For a
typical raised fireplace of 36" (915mm), place the fireplace on a platform 25.625" (651mm) tall.
© Travis Industries
Installation
(for qualified installers only)
4140108