Gas Line Requirements; Fuel; Gas Line Connection; Gas Inlet Pressure - Travis Industries 4415 HO GSR2 Installation Manual

Travis industries fireplace
Hide thumbs Also See for 4415 HO GSR2:
Table of Contents

Advertisement

14

Gas Line Requirements

MASSACHUSETTS INSTALLATIONS - WARNING:
THIS PRODUCT MUST BE INSTALLED BY A LICENSED PLUMBER OR GAS FITTER WHEN INSTALLED WITHIN THE
COMMONWEALTH OF MASSACHUSETTS.
OTHER MASSACHUSETTS CODE REQUIREMENTS:
Flexible connector must not be longer than 36 inches.
Shutoff valve must be a "T" handle gas cock.
Only direct vent sealed combustion products are approved for bedrooms or bathrooms.
Fireplace dampers must be removed or welded in the open position prior to the installation of a fireplace insert or gas log.
A carbon monoxide (CO) detector is required in the same room as the appliance.
The gas line must be installed in accordance with all local codes, if any; if not, follow ANSI 223.1 and NFPA
54(88), in Canada follow CSA B149.1 and the requirements listed below.
The fireplace and gas control valve must be disconnected from the gas supply piping during any pressure
testing of that system at test pressures in excess of 1/2 psig (3.5 kPA). For pressures under 1/2 psig (3.5
kPA), isolate the gas supply piping by closing the manual shutoff valve.
Leak test all gas line joints and the gas control valve prior to and after starting the fireplace.
This unit has been listed using the included internal gas shutoff valve.

Fuel

This fireplace is designed either for natural gas or for propane (but not for both).

Gas Line Connection

Installation must be performed by a qualified installer, service agency or the gas supplier (In Massachusetts a licensed
plumber/gasfitter).

Gas Inlet Pressure

If the pressure is not sufficient, make sure the piping used is large enough, the supply regulator is adequately adjusted,
and the total gas load for the residence does not exceed the amount supplied.
The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas
at the input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.
© Travis Industries
Installation
(for qualified installers only)
Maximum Input Pressure
Natural Gas
7" W.C. (1.74 kPA)
Propane
13" W.C. (3.23 kPA)

Directions for Connecting a Gas Pressure Test Gauge

The gas control valve (shown to the left) has two accessible ports for testing
line pressure and output pressure. Loosen the brass screw on either test port
and place a 5/16" i.d. rubber or plastic tubing over the tapered test port.
Connect the tubing to the test gauge.
WARNING: The brass screw must be tightened after testing to prevent gas
leakage.
Output pressure
Input pressure
Minimum Input Pressure
5.5" W.C. (1.37 kPA)
11" W.C. (2.74 kPA)
4140108
100-01353