How it works . . .

Control module
The control module (used on
boiler limit circuit to operate the boiler circulator, pilot burner, gas valve and vent damper. When room thermostat
calls for heat, the control module starts the system circulator and activates the vent damper (causing it to drive
open).
When the vent damper has opened completely, the control module opens the pilot valve and activates pilot ignition
spark.
The control module allows up to 15 seconds to establish pilot flame. If flame is not sensed within 15 seconds, the
control module will turn off the gas valve, flash the Flame light, and immediately start a new cycle. This will
continue indefinitely until pilot flame is established or power is interrupted. Once pilot flame is proven, the control
module opens the gas valve to allow main burner flame.
When the room thermostat is satisfied, the control module turns off the gas valve and deactivates the vent damper
(causing it to close).
The control module indicator lights show normal sequence when the lights are on steady. When a problem occurs,
the control module flashes combinations of lights to indicate the most likely reason for the problem. See page 52
for details.
Standing pilot boilers
satisfied, the gas valve and vent damper will open on a call for heat and close afterwards.
Transformer
The control transformer reduces line voltage to 24 volts for the gas valve and limit circuit.
Draft hood
The draft hood provides a minimum draft for the boiler, assuring adequate air for combustion if installed in
accordance with manual and not modified in any way.
Spill switch
The spill switch will shut down the boiler (requiring manual reset of the switch reset button) if the vent system
becomes blocked.
Water temperature limit switch
The water temperature limit switch turns off the gas valve if the temperature in the boiler goes above its setting.
(The circulator will continue to run as long as there is a call for heat.)
Boiler circulator
The boiler circulator circulates water through the external (system) piping. The circulator is shipped loose, and
can be mounted on either the boiler supply or return piping. The factory-installed circulator wiring harness
provides ample length for either location.
boiler is not operated for 30 days, the control module will power the circulator for 30 seconds, then turn off.
Vent damper
The vent damper closes during off cycles to reduce heat loss from the house up the vent.
Other boiler components:
a supply to system
b return from system
c flue outlet
d burner manifold
e gas valve
2
CGa Gas-Fired Water Boiler
spark-ignited pilot boilers
(controls not shown) use the pilot thermocouple to prove flame. If the thermocouple is
NOTE
f
g relief valve
h air vent connection
i
j
) responds to signals from the room thermostat and
— The control module provides a pump exercising routine. If the
pressure/temperature gauge
flame rollout switch
burner orifice
k pilot burner, typical
l
stainless steel burners
m cast iron boiler sections
n flue collector
o junction box
Part Number 550-110-593/1099