11c
Troubleshooting
Chart 4 — Spark-ignited pilot —
— If
POWER
— If
POWER
Electrical shock hazard — Wherever you see
instructions could result in severe personal injury, death or substantial property damage.
• Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.
• Thermostat should call for heat and appropriate zone valves open. The
• Wait 45 seconds.
Does vent damper operate?
No
• Remove DAMPER plug ( Figure 30, Item 6, page 53 )
from plug receptacle of control module.
• Place voltmeter leads across the top two pins (1 and 4)
of the DAMPER receptacle.
Does the voltmeter indicate 24 VAC?
No
Are the
TSTAT CIRC
Yes
• Replace control
module.
• Retest.
56
CGa Gas-Fired Water Boiler
light is flashing: Usually indicates vent damper failed to prove open within 5 minutes —
light is steady: Usually indicates vent damper closed during run cycle —
Does vent damper operate?
No
Yes
Yes
• Try reseating plug in
module receptacle and
restart.
• If vent damper still does
not work, replace vent
damper assembly or
actuator.
• Retest.
and
lights on steady?
LIMIT
No
• Make sure thermostat is
calling for heat. If lights
still don't come on, see
Chart 7.
spark-ignited pilot boilers
DAMPER
light flashing
▲TURN OFF
POWER▲, follow the instructions. Failure to follow
TSTAT CIRC
• Wait 5 minutes.
Is
No
• Boiler should be in
normal operating
sequence.
• Observe operation until
thermostat is satisfied.
• Replace vent damper
assembly or actuator.
• Retest.
and
LIMIT
lights should come on.
Yes
DAMPER
light flashing?
Yes
Does vent damper actuator
indicator show damper is
open?
No
• Remove damper wiring
plug at damper and firmly
reconnect.
• Recheck boiler operation.
• If problem persists,
replace vent damper
assembly or actuator.
Part Number 550-110-593/1099