I. General Requirements
A. Furnish and install (
operate under induced draft.
B. Install boiler-burner unit(s) in compliance with manufacturers installation instructions.
All work must be done in a neat and workman like manner.
C. Weil-McLain qty.( ) CGt ( ) PIN boiler(s) capable of burning natural gas at 5 to
13"w.c.
1. Packaged boiler (standard).
2. Natural or propane gas fired.
3. Water.
4. Minimum 82% efficiency.
5. Induced draft.
6. Built-in Tankless Domestic Water Heater
D. Boiler(s) shall have I=B=R Hydronics Institute gross output(s) at 100% firing rate –
108 MBH per boiler.
E. Boiler(s) shall be manufactured by ISO 9001 registered company to conform to
Section IV of
the ASME Boiler and Pressure Vessel Code.
1. Individual sections (and section assembly) to be hydrostatically pressure tested
at factory in accordance with ASME requirements.
2. Maximum allowable working pressure 50 PSIG water and cast as part of
section with ASME symbol.
F. Regulatory Requirements
1. Boiler(s) and controls to comply with applicable regulations.
G. Submittals
1. Submit shop drawings and product data.
2.
Submittal packet to include boiler (and burner) manufacturer descriptive
literature, installation instructions, operating instructions, and maintenance
instructions.
II.
Product
1
CGt SERIES BOILER
SUGGESTED SPECIFICATIONS
) low pressure packaged cast iron sectional boiler(s) that

Advertisement

loading

Summary of Contents for Weil-McLain GOLD CGt SERIES

  • Page 1 B. Install boiler-burner unit(s) in compliance with manufacturers installation instructions. All work must be done in a neat and workman like manner. C. Weil-McLain qty.( ) CGt ( ) PIN boiler(s) capable of burning natural gas at 5 to 13”w.c.
  • Page 2 Acceptable boiler/burner manufacturer(s) include(s): 1. Weil-McLain only, as specified in Part 1, Paragraph C. a) Other manufacturer(s) or other Weil-McLain boiler(s) must comply with specifying engineer’s requirements, including: Full intent of these specifications, and provide complete submittal including literature, wiring diagrams, fuel piping diagrams, and a list of similar installations.
  • Page 3 4) Integrated spark module for blower control with indicator lights for easy troubleshooting. Boiler Manuals: 1. Boiler, gas control and user’s information manual. 2. Venting supplements and instructions. Weil-McLain 500 Blaine Street Michigan City, IN 46360-2388 http://www.weil-mclain.com C-879 (0700)

This manual is also suitable for:

Cgt series