How it works
• • •
(!)
Control
module
The control module responds to
signals from
the room
thermostat,
air
pressure
switch
and
boiler
limit circuit to operate
the
boiler
circulator,!ilot
burner,
gas valve and inducer.
When room
thermostat
calls
for
heat, the
control
module
starts
the
system circulator
an inducer.
The
control
module nms the inducer
long
enough to purge the
boiler
flue passages,
then
opens the
pilot
valve
and
activates
pilot
ignition spark.
For
natural
gas,
the
control
module allows up to IS seconds to
establish pilot
flame. If flame is
not sensed within IS
seconds,
the
control
module
will turn off
the gas valve,
flash
the Flame light,
and then enter
a
IS-second
postpurge. The
control
module
will then
start a new cycle. This
will
continue indefinitely
until pilot
flame is
established or
power is
interrupted
.
Once
pilot
flame is proven, the
control
module opens the gas valve to allow
main burner
flame.
For
propane gas, the
control
module allows up to IS seconds to
establish pilot
flame. If flame is
not
sensed
within IS
seconds,
the
control
module
will tum
off the gas valve,
flash
the Flante light,
wait I
minute,
then
start a new cycle. If flame is
still not
sensed after the
second
trial, two more attempts are made
with S
minute
wait
periods
in
between. If flante is
not
sensed
after
4
tries,
control will lockout
and
flash all
lights.
Control must
be manually
reset
to
place
back
into service. Once
pilot
flame
is proven, the
control
module opens the gas valve to allow
main
burner flante.
When
the
room thermostat
is satisfied, the
control
module turns off the gas valve,
operates
the inducer
for
a IS-second
postpurge
and
waits
for the
next
heat call.
The
control
module indicator
lights show
normal sequence
when
the lights
are
on
steady.
When
a
problem
occurs,
the
control
module flashes combinations
of
lights to indicate the
most
likely
reason for
the
problem
(see page
49).
@
Transfonner
The
control transformer
reduces
line voltage to
24
volts for the gas valve and limit circuit.
@
Induce
r
The inducer pulls flue gases
through
the boiler, causing
air
to be
pulled in
through the
boiler air
openings. The
inducer
pushes
the flue gases
through
the
vent
pipe as
well
@
Air pressure sw it ch
The air pressure
switch signals
the
control
module, telling the
control module
whether
the
inducer
is
working
correctly
or
the vent is blocked.
@
Water
temperature
limit sensor
The
water
temperature
limit
sensor
provides a
signal
to the
control module
to turn
off
the
gas valve
if
the temperature
in
the
boiler
goes
above its setting. (The
circulator will
continue to run
as long as
there is a call for heat.)
@
Boller circulator
The boiler
circulator
circulates water through
the
external
(system)
piping.
The
circulator
is
shipped loose,
and
can
be mounted
on
either
the
boiler
supply or return piping.
The factory-installed
circulator
wiring
harness
provides ample
length
for either
location.
NOTE
-
The control
module provides a pump
exercising
routine. If the boiler
is
not
operated
for
30
days, the
control
module
will
power
the
circulator
for
30
seconds,
then
tum
off.
Timer relay
- CGI
4
Only
The timer relays delays high fire
for
60
seconds.
Other
boile
r components:
2
a
supply
to
system
b
return
from
system
c
stainless steel
burners
d
flue
outlet
e
gas valve
f
pressure/temperature gauge
g
relief valve
h
air
vent
connection
i
flame
rollout thermal
fuse
element
(TFE)
j
burner
shield
k
pilot burner and
bracket
1
gas
manifold
m
cast
iron
boiler sections
n
flue
collector
o
junction
box
Part
Number 550-142-780/0712

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cgi-25Cgi-5Cgi-4Cgi-6Cgi-8Cgi-7

Table of Contents