Weil-McLain GOLD CGa Installation And Maintenance Manual page 67

Gas-fired
Hide thumbs Also See for GOLD CGa:
Table of Contents

Advertisement

Boiler Manual
13b
Ratings
Boiler
Input
DOE
model
(Btuh)
Heating
number
capacity
(Btuh)
(Note 1)
(Note 2)
CGa-25
52,000
44,000
CGa-3
70,000
59,000
CGa-4
105,000
88,000 105,000
CGa-5
140,000
117,000 140,000 117,000 126,000 105,000 102,000
CGa-6
175,000
146,000 175,000 146,000 157,500 131,000 127,000
CGa-7
210,000
175,000 210,000 175,000 189,000 157,000 152,000
CGa-8
245,000
204,000 245,000 204,000 220,500 183,000 177,000
Notes
1
. See Table 7 for available pilot systems. The suffix shown
in the table is added to the boiler model number. (Not
available for millivolt systems.)
2. Based on standard test procedures prescribed by the
United States Department of Energy.
3. Net I=B=R ratings are based on net installed radiation of
sufficient quantity for the requirements of the building
and nothing need be added for normal piping and pickup.
Ratings are based on a piping and pickup allowance of
1.15. An additional allowance should be made for unusual
piping and pickup loads.
Install CGa boilers for residential radiant panel systems, converted gravity heating systems or other low water
temperature applications per instructions in this manual to avoid damage due to condensation.
CGa boilers are CSA design certified for installation on combustible flooring.
CGa boilers are ASME rated for 50 psig working pressure.
Part Number 550-110-593/1099
0–2,000 feet
2,000–4,500 feet
altitude
altitude
Input
Output
Input
(Btuh)
(Btuh)
(Btuh)
52,000
44,000
46,800
70,000
59,000
63,000
88,000
94,500
Net
Boiler
I=B=R
water
ratings
content
(Btuh)
(gallons)
Output
(Btuh)
(Note 3)
39,000
38,000
1.5
53,000
51,000
1.5
79,000
77,000
2.1
2.7
3.3
3.8
4.4
Table 7 Ignition system model suffixes
Pilot ignition system
Standing pilot
Spark-ignited pilot
DOE
Seasonal efficiency
(% A.F.U.E)
breeching
SPDN
SPDL
PIDN
81.5
83.3
84.0
4"I.D. x 20'
81.6
83.7
84.0
4"I.D. x 20'
81.7
83.7
84.0
5"I.D. x 20'
81.8
83.7
83.5
6"I.D. x 20'
81.9
83.6
83.2
6"I.D. x 20'
82.0
83.6
83.0
7"I.D. x 20'
82.1
83.6
82.7
7"I.D. x 20'
Natural gas
Propane gas
SPDN
PIDN
Not available
DOE
Chimney
and
size
SPDL
67

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents