Service And Maintenance - Weil-McLain GOLD CGa Installation And Maintenance Manual

Gas-fired
Hide thumbs Also See for GOLD CGa:
Table of Contents

Advertisement

GOLD
10a
Service and maintenance —
Table 6 Service and maintenance schedules (service technician and user)
Follow the
shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or
system. Failure to follow the directions in this manual and component literature could result in severe personal
injury, death or substantial property damage.
44
CGa Gas-Fired Water Boiler
Service technician
(see following pages for instructions)
Inspect:
• Reported problems
• Boiler area
• Air openings
• Flue gas vent system
• Pilot and main burner flames
• Water piping
• Boiler heating surfaces
• Burners and base
Service:
• Oiled-bearing circulators
Start-up:
• Perform start-up per manual
Check/test:
• Gas piping
• Cold fill and operating pressures
• Air vents and air elimination
• Limit controls and cutoffs
• Expansion tank
• Boiler relief valve
Review:
• Review with owner

Service and maintenance

(see CGa User's Information Manual for instructions)
Daily
Monthly
Periodically
Every 6 months
End of season
procedures given throughout this manual and in component literature
schedule
Owner maintenance
• Check boiler area
• Check air openings
• Check boiler pressure/
temperature gauge
• Check boiler interior piping
• Check venting system
• Check air vents
• Check boiler relief valve
• Check automatic air vents (if
used)
• Test low water cutoff (if used)
• Operate relief valve
• Shut down procedure
Part Number 550-110-593/1099

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents