Gas piping

Connecting gas supply piping to boiler
1. Remove jacket front panel and refer to
a.
at inlet of gas connection to boiler. Where local
Install drip leg
utility requires drip leg to be extended to the floor, use appropriate
length of pipe between cap and tee.
b.
Install ground joint union
c.
Install manual shutoff valve
jacket when required by local codes or utility requirements.
d.
In Canada
— When using manual main shutoff valve, it
by the installer.
identified
2.
with hangers, not by boiler or its accessories.
Support piping
3.
from gas supply piping.
Purge all air
4. Before placing boiler in operation,
for leaks .
a.
Close manual main shutoff valve
less than 13" w.c.
b.
Disconnect boiler and gas valve from gas supply piping
any pressure testing greater than 13" w.c.
Do not check for gas leaks with an open flame
Use bubble test. Failure to use bubble test or check for
gas leaks can cause severe personal injury, death or
substantial property damage.
5.
Use pipe dope compatible with propane gases.
to male threads of pipe joints so that pipe dope does not block gas flow.
Failure to apply pipe dope
in severe personal injury, death or substantial property
damage.
Table 4 Pipe capacity for 0.60 specific gravity natural gas
Capacity of pipe for pipe size of:
Gas pipe
(Capacity in cubic feet gas per hour)
length
(feet)
½"
10
132
20
92
30
73
40
63
50
56
75
45
100
38
150
31
26
CGa Gas-Fired Water Boiler
to pipe gas to boiler.
Figure 19
for servicing, when required.
in gas supply piping outside boiler
check boiler and its gas connection
during any pressure testing at
Apply sparingly only
as detailed above can result
¾"
1"
1¼"
278
520
1050
190
350
730
152
285
590
130
245
500
115
215
440
93
175
360
79
150
305
64
120
250
Natural Gas:
1. Refer to
Table 4
on rated boiler input (divide by 1,000 to obtain cubic
feet per hour).
gravity 0.60, with a pressure drop through the
gas piping of 0.30" w.c.
sizing information, refer to ANSI Z223.1 (or B149.1
or B149.2 for Canadian installations).
2. Inlet pressure required at gas valve inlet:
must be
Maximum: 13" w.c.
Minimum: 5" w.c.
Manifold gas pressure: 3.5" w.c.
3. Install 100% lockup gas pressure regulator in supply
line
if inlet pressure exceeds 13" w.c.
13" w.c. maximum.
Propane Gas:
1. Contact gas supplier to size pipes, tanks and 100%
lockup gas pressure regulator.
during
2. Adjust propane supply regulator provided by gas
supplier for 13" w.c. maximum pressure.
3. Inlet pressure required at gas valve inlet:
Maximum: 13" w.c.
Minimum: 11" w.c.
Manifold gas pressure: 10" w.c.
Figure 19
Gas supply piping
1½"
1600
1100
860
760
670
545
460
380
for pipe length and diameter. Base
is only for gas with
Table 4
specific
For additional gas pipe
Adjust for
Manual main
shutoff gas valve
(when required)
Ground joint union
(when required)
Tee
Nipple
Cap
Part Number 550-110-593/1099