Sensitivity Setting
2
0 or 3
4
5
1 or 6
7
Table 8.1: Sensitivity and Response
9

Specifications

Electrical
Alarm Current (Receiver)
Standby Current
Operating Voltage
Alarm contacts
Auxiliary alarm contacts
Trouble contacts
Environmental
Environment
Relative humidity
Temperature
(storage and operating)
2014.01 | 06 | F.01U.068.899
Must Not Alarm
0% (no filter)
0% (no filter)
20% (filter)
20% (filter)
40% (filter)
40% (filter)
D296: 70 mA maximum at 24 VDC
D297: 75 mA at 12 VDC
D296 Receiver: 45 mA at 24 VDC
D296 Transmitter: 20 mA at 24 VDC
D297 Receiver: 50 mA at 12 VDC
D297 Transmitter: 20 mA at 12 VDC
D296: 18.0 VDC to 32.0 VDC
D297: 10.2 VDC to 15.0 VDC
Normally Open (N/O) contacts rated 1 A, 60 VDC maximum
for DC resistive loads; do not use with capacitive or inductive
loads
Normally Open (N/O) contacts rated 1 A, 60 VDC maximum
for DC resistive loads; do not use with capacitive or inductive
loads
Normally Closed (N/C) contacts rated 1 A, 60 VDC maximum
for DC resistive loads; do not use with capacitive or inductive
loads
Indoor, dry
0% to 95%, non‑condensing
-22°F to +130°F (-30°C to +54°C)
For UL Listed installations, the range is +32°F to +130°F (0°C
to +54°C)
Installation Instructions
Long-range Beam Smoke Detectors
Must Alarm
40% filter
60% filter
60% filter
80% filter
80% filter
80% filter