D. Use of Flex Vent
The fl ex vent must be supported with
the spacing between support intervals
not exceeding 4 feet, with no more
than ½ inch sag between supports.
A support is required at each change
in venting direction, and in any location
where it is necessary to maintain the
necessary clearance to combustibles.
A simple "up and out" installation (Fig-
ure 5.3) requires only enough support
to maintain the necessary clearance
to combustibles. However, the vent at-
tachment point and the fi restop loca-
tion are considered to be supports.
14
FLEX-VENT
Figure 5.3
Heat & Glo • SL-550 / 750 / 950TR-E • 2118-900 Rev. D • 6/07
3 in. CLEARANCE
TERMINATION
CAP
1 in.
CLEARANCE