E. Use of Flex Vent (SLP-FLEX Series 6-5/8
Inch)
The flex vent must be supported with the spacing between
support intervals not exceeding 4 feet, with no more than
1/2 inch sag between supports.
A support is required at each change in venting direction,
and in any location where it is necessary to maintain the
necessary clearance to combustibles. A simple "up and
out" installation (Figure 4.8) requires only enough support
to maintain the necessary clearance to combustibles.
However, the vent attachment point and the firestop loca-
tion are considered to be supports.
TERMINATION
CAP
3 in. CLEARANCE
FLEX-VENT
1 in.
CLEARANCE
Figure 4.8 Flex Vent Pipe - Generic Fireplace Shown
Heat & Glo • SL-5F-IFT, SL-7F-IFT Installation Manual • 2638-980 Rev. H • 6/22