Dst1 Series Monitoring; Monitoring The Dst1-Id12Sl-1 - Omron NE1A-EDR01 Operation Manual

Ne1a series ethernet/ip-devicenet router
Table of Contents

Advertisement

DST1 Series Monitoring

4-7

DST1 Series Monitoring

4-7-1

Monitoring the DST1-ID12SL-1

Safety input monitor
Safety input status
Overall status (See note 1.)
Safety input error cause
(See note 2.)
Note
66
DST1-ID12SL-1, DST1-MD16SL-1, DST1-MRD08SL-1, or DST1-XD0808SL-
1 data can be monitored by changing to the values shown below the commu-
nications messages (service code, class ID, instance ID, and request data
(attribute ID)) indicated in 4-5 Sample Ladder Programs.
Service code
Input value/
0E hex
status
Error cause 0E hex
(1) Overall Status
Read Data Format (Read Size: 1 Byte)
+0
Status
Bit
0
Input Power Supply Voltage Monitor Flag
OFF: I/O power supply ON, ON: I/O power supply OFF
1
Output Power Supply Voltage Monitor Flag
OFF: I/O power supply ON, ON: I/O power supply OFF
2
Network Power Supply Voltage Monitor Error Flag
OFF: Normal (higher than monitor set value), ON: Error (equal to or
higher than monitor
3
Module Maintenance Flag
OFF: Within range (lower than monitor set value), ON: Out of range
(equal to or lower than monitor set value)
4
Reserved
5
I/O Error Flag
OFF: Normal (all I/O points normal), ON: Error (one or more I/O points
abnormal)
6
Operation Time Monitor Error Flag
OFF: Within range (all I/O sets lower than monitor set value), ON: Out
of range (one or more I/O sets equal to or greater than monitor set
value)
7
Connected Device Maintenance Flag
OFF: Within range (all I/O points lower than monitor set value), ON:
Out of range (one or more I/O points equal to or greater than monitor
set value)
(2) Safety Input Error Cause
When an error is indicated for the safety input status, the cause of the er-
ror can be acquired by reading this information.
Specify the terminal number for which the error cause is to be acquired,
plus 1, for the instance ID specified at that time. For example, to acquire
the error cause for terminal No. 0, specify 01 hex for the instance ID.
Class ID
Instance ID
04 hex
Refer to the table in
note 3.
3D hex
01 to 0C hex
Status
Meaning
Section 4-7
Request data
(attribute ID)
03 hex
6E hex

Advertisement

Table of Contents
loading

Table of Contents