Settings From The Network Configurator - Omron NE1A-EDR01 Operation Manual

Ne1a series ethernet/ip-devicenet router
Table of Contents

Advertisement

Settings from the Network Configurator

The following parameters can be set from the Network Configurator.
Note Network Configurator version 2.0 or higher is required to set the ED Router parameters.
Network Configurator
version 2.0 or higher
Classification
Setting
ED Router
Displayed address
device settings
UDP port number
DeviceNet set-
Baud rate for software
tings
settings
Node address for soft-
ware settings
Ethernet
IP address setting
(EtherNet/IP)
method
settings
DNS usage
IP address
Network mask
Default gateway
Primary DNS server
Secondary DNS server
Domain name
LINK settings
Appendix B
EtherNet/IP or DeviceNet
Select whether the EtherNet/IP IP address
or the DeviceNet node address is to be dis-
played at the ED Router 7-segment display
under normal conditions.
Set a number from 1,024 to 65,535 as the
UDP port number to be used for device
access by UDP.
Select 125 Kbit/s, 250 Kbit/s, or 500 Kbit/s.
Set an address from 0 to 63.
Select either ìacquire from BOOTP or use
the next IP addressî as the IP address set-
ting method.
Select to either use or not use DNS.
Specify the IP address for when use the
next IP addressî is selected as the IP
address setting method.
Specify the DNS server for when use DNS
is selected.
Select Auto, 10-Mbit/s half duplex, 10-Mbit/s
full duplex, 100-Mbit/s half duplex, or 100-
Mbit/s full duplex as the Ethernet (EtherNet/
IP) baud rate.
ED Router
Description
Initial value
Reference
DeviceNet node
2-5 ED Router
address
Settings
64,000
125 Kbit/s
2-3 Connect-
ing to
DeviceNet.
63 (decimal)
Use the next IP
2-4 Connect-
address
ing to Ethernet
(EtherNet/IP)
Do not use DNS
192.168.250.1
255.255.255.0
None (0.0.0.0)
None (0.0.0.0)
None (0.0.0.0)
None (0000 hex)
A maximum of 48
ASCII characters
can be set.
Auto
83