Seven-Segment Display - Omron NE1A-EDR01 Operation Manual

Ne1a series ethernet/ip-devicenet router
Table of Contents

Advertisement

Status Indicators
3-1-2

Seven-segment Display

Normal Status
Error Status
Displaying the EtherNet/IP IP Address and the DeviceNet Node Address
This section describes the meanings of the 7-segment display.
When no error has occurred and communications are enabled, the ED Router
DeviceNet node address is displayed as the initial status on the 7-segment
display.
• Display Example: When the Node Address Is 01
The rightmost byte of the EtherNet/IP IP address can be displayed by a set-
ting from the Network Configurator.
When an error occurs, the error code is displayed following Er. If multiple
errors occur, the error codes are displayed in order.
• Display Example: When the Error Codes Are d6 and E0
1000 ms
Not lit
1000 ms
for
100 ms.
(Error code)
(Error)
The EtherNet/IP IP address and the DeviceNet node address can be dis-
played on the 7-segment display by pressing the service switch for 1 s or
longer before releasing it.
• Display Example: EtherNet/IP IP Address
• Display Example: EtherNet/IP IP Address when BOOTP Is Set
• Display Example: DeviceNet Node Address
Not lit
Not lit
1000 ms
for
for
100 ms.
100 ms.
(Error)
Section 3-1
Not lit
for
300 ms.
(Error code)
27