Installation; Requirements For Installation And Wiring; Mounting To The Control Panel - Omron NE1A-EDR01 Operation Manual

Ne1a series ethernet/ip-devicenet router
Table of Contents

Advertisement

Installation

2-1

Installation

2-1-1

Requirements for Installation and Wiring

Installation and
Storage Environment
2-1-2

Mounting to the Control Panel

6
Take the following into account during installation to improve the reliability of
the system and to fully utilize the system's capabilities.
Do not use or store the ED Router in the following locations.
• Locations subject to direct sunlight
• Locations subject to temperatures or humidity outside the ranges speci-
fied in the specifications
• Locations subject to condensation as the result of severe changes in tem-
perature
• Locations subject to corrosive or flammable gases
• Locations subject to dust (especially iron dust) or salts
• Locations subject to water, oil, or chemicals
• Locations subject to shock or vibration
Take appropriate and sufficient measures when installing systems in the fol-
lowing locations. Inappropriate and insufficient measures may result in mal-
function.
• Locations subject to static electricity or other forms of noise
• Locations subject to strong electromagnetic fields
• Locations subject to possible exposure to radioactivity
• Locations close to power supplies
• Use the ED Router in an enclosure with IP54 degree of protection or
higher according to IEC/EN 60529.
• Use DIN Track (TH35-7.5/TH35-15 according to IEC 60715) to mount the
ED Router in the control panel. Mount the Router to the DIN Track using
PFP-M End Plates (not included with the ED Router) to prevent it from
falling off the DIN Track because of vibration.
• Provide sufficient space around the ED Router for ventilation and wiring,
at least 5 mm at the sides and at least 50 mm at the top and bottom.
• The ED Router can be mounted in any direction.