Wiring
2-2-4

Ethernet (EtherNet/IP) Network Installation

Basic Installation
Precautions
Recommended
Network Devices
Part
Maker
Switching Hub Cisco Systems, Inc.
Contec USA, Inc.
Phoenix Contact
Twisted-pair
100BASE-TX
cable
Fujikura
EtherNet/IP compliant cable
Connectors
STP Plug
(Modular plug)
Panduit Corporation
Boots
Tsuko Company
Precautions
Precautions on Laying
Twisted-pair Cable
12
Note
Refer to the DeviceNet Operation Manual (W267) for further information on
wiring.
• Take the greatest care when installing the Ethernet System, being sure to
follow ISO 8802-3 specifications. You must obtain a copy of these specifi-
cations and be sure you understand them before attempting to install an
Ethernet System.
• Unless you are already experienced in installing communications sys-
tems, we strongly recommend that you employ a professional to install
your system.
• Do not install Ethernet equipment near sources of noise. If a noisy envi-
ronment is unavoidable, take adequate measures against noise interfer-
ence, such as installing network components in grounded metal cases or
using optical cable in the system.
The following table shows the devices recommended for use with the ED
Router.
Consult the manufacturer.
Consult the manufacturer.
Consult the manufacturer.
F-LINK-E 0.5mm × 4P
MPS588
MK boot (IV) LV
Note
• Ask the switching hub manufacturer for setting procedures for the switch-
ing hub.
• Install the switching hub so that its environmental resistance capabilities
are not exceeded.
Ask the switching hub manufacturer for information on the environmental
resistance of the switch hub.
• Noise resistance may be reduced by ground loops, which can occur due
to improper shield connections and grounding. Ground the shield at one
location, as shown in the following diagram.
• Do not connect the shield to the ED Router connector.
• If a cable connects two hubs, connect the shields at only one end.
Model number