Wiring

2-2

Wiring

2-2-1

General Instructions on Wiring

Precaution:
2-2-2

Wiring the Power Supply

Wire Sizes
Recommended
Materials and Tools
Insulated Pin Terminals
Note
Model of pin terminal
AI 0,34-8TQ
AI 0,5-10WH
AI 0,75-10GY
AI 1-10RD
AI 1,5-10BK
• To prevent wire clippings from getting into the ED Router, do not remove
the label on the ED Router before wiring has been completed.
• After wiring has been completed, be sure to remove the label from the
Controller to enable heat dissipation for proper cooling.
• Disconnect the ED Router from the power supply before starting any wir-
ing operations. Devices connected to the ED Router may operate unex-
pectedly if wiring is performed with the power supply connected.
• Be careful not to get your fingers caught when attaching connectors.
• Faulty wiring can result in a loss of safety functions. Be sure to perform
the wiring correctly, and check it before operation.
Use the following wires.
Solid wire
0.2 to 2.5 mm
Stranded (flexible) wire 0.34 to 1.5 mm
Stranded wires should be prepared by attaching ferrules with plastic
insulation collars (DIN 46228-4 standard compatible) before con-
necting them.
Use a pin terminal with an insulated cover compliant with the DIN 46228-4
standard. Pin terminals similar in appearance but not compliant with the stan-
dard may not match the terminal block on the ED Router Controller. (The wir-
ing dimensions are rough standards. Confirm the dimensions beforehand.)
Use wires of the same diameter if two-wire pin terminals are used.
(1) When wiring with pin terminals, be sure to insert pin terminals all the way
into the terminal block.
(2) When using two-wire pin terminals, use wires of the same diameter.
(3) When using two-wire pin terminals, insert the pin terminal so that metal
portion of the pin terminal is inserted straight into the terminal block, i.e.,
so that the long sides of the insulating cover are vertical.
Reference Specifications (Product Specifications for Phoenix Contact)
Wire dimensions
Cross-
AWG
Stripped
sectional
length of
area of
insulation
conductor
2
(mm
)
0.34
22
10
0.5
20
10
0.75
18
10
1.0
18
10
1.5
16
10
2
(AWG 24 to AWG 12)
2
(AWG 22 to AWG 16)
Pin terminal specifications
Overall
Length of
length L1
metal
(mm)
part L2
(mm)
(mm)
12.5
8
16
10
16
10
16
10
18
10
Section 2-2
Inner
Inner
diameter of
diameter of
conductor
insulative
D1 (mm)
cover D2
(mm)
0.8
2.0
1.1
2.5
1.3
2.8
1.5
3.0
1.8
3.4
*1
9