GENERAL

The IFS-2600 in its most basic form comprises of three boards, the main control board, the main termination
board and the power supply board.
The main control board contains the Microprocessor, EPROM, RAM and E
has the liquid crystal display and keypad attached. All of the "delicate" electronics have been placed on this
board. The main control board complete with the inner door is easily removed during installation to avoid
damage and allow greater access to the field terminals.
The main termination board contains the one power supply for 5V logic, and connectors for a Power Supply
and Battery Charger daughter board, the first eight zones, all common outputs and the printer interface. All
charger settings, fuses etc are located on this board. The Power Supply and Battery Charger board contains
two switch mode regulators, 26.5V for the panel power, 27.3V for the battery charger.
Up to seven (7) zone expansion boards can be added to the system to increase its detection capability. These
boards contain the same electronics as on the main termination board for zone scanning. Addressing is by a
jumper that selects which group of eight zones the board refers to.
Up to four (4) zone indicator boards can also be added. These boards will display the status of the zone
expansion boards fitted.
Up to eight (8) relay boards can be added. These boards contain 8 change-over relay contacts, each rated at
1 amp. These boards require no addressing, as they work on a serial data chain. Output 1 is the closest
output to the main board.
NOTE This product utilises state of the art components and materials and therefore boards must be returned
to our factory for proper troubleshooting, repair and retesting. Field component level repairs are not
recommended and would void all warranties on the product.

TRANSIENT SUPPRESSION

The IFS-2600's superior transient protection comprises of Dual Transorb input traps, inductive paths on
incoming PCB tracks, circuit board planes and metal oxide varistors on outputs. These devices are all self-
resetting.

CURRENT CONSUMPTION

Zones Fitted
Quiescent Current
8
16
24
32
40
48
56
64
Note:
1:
Each installation would require individual battery calculations to be performed for load capacity and
power supply capacity.
2:
Each IFS-717 relay board, can add 370 mA (in alarm and quiescent) current per board.
P/N 10069 ECN08-0066
Quiescent + 2 AZF'S in alarm +1A of Bell +1 Amp ACF
150 mA
250 mA
350 mA
450 mA
550 mA
650 mA
750 mA
850 mA

TECHNICAL DESCRIPTION

2
ROM. The main control board also
2.23 AMPS
2.33 AMPS
2.43 AMPS
2.53 AMPS
2.63 AMPS
2.73 AMPS
2.83 AMPS
2.93 AMPS
Page 11