Instructions To Operators; Indicators - Honeywell NOTIFIER IFS-2600 Technical Installation Manual

Fire indicator panel
Table of Contents

Advertisement

Page 20

INDICATORS

Qty
Descriptor
1
MAINS ON
1
BATTERY
FAULT
1
PSU FAULT
1
CHARGER
LOW
1
COMMON
FAULT
1
ACF ACT
1
ACF FLT
1
ACF ISO
1
Bell ACT
1
Bell FLT
1
Bell ISO
1
Warning
System ACT
1
Warning
System FLT
1
Warning
System ISO
8
ALARM LEDS
8
FAULT LEDS
8
ISOLATE LEDS
P/N 10069 ECN08-0066

INSTRUCTIONS TO OPERATORS

Colour
Green
Illuminates when there is 200/220/240 VAC supply to
the panel.
Yellow
Illuminates if the battery fails a battery test.
Illuminates if batteries are disconnected >30
seconds.
Illuminates if batteries are short circuit >30 seconds.
Yellow
Illuminates if the power supply is outside the
manufacturers range.
Yellow
Illuminates if the battery charger is outside the
recommended float charge voltage.
Yellow
Illuminates if;
Any un-isolated zone goes into fault.
ACF output is open or short circuit
Bell output is open or short circuit
Warning System output is open or short circuit
Battery Fault
Charger Fault
Power Supply Fault
MAF Isolate Input is Open Circuit
Configuration Fault
Red
Illuminates if the ACF output has been activated.
Yellow
Illuminates if the ancillary circuit is open or short
circuit. The LED will extinguish when the load is
restored.
Yellow
Illuminates if the ancillary output has been manually
isolated.
Red
Illuminates when the bell output has been energised.
Yellow
Illuminates if the bell circuit is open or short circuit.
The LED will extinguish when the load is restored.
Yellow
Illuminates if the bell output has been manually
isolated.
Red
Illuminates if the Warning System output has been
energised.
Yellow
Illuminates if the Warning System circuit is open or
short circuit. The LED will extinguish if the load is
restored.
Yellow
Illuminates if the Warning System has been manually
isolated.
Red
This LED will flash if it's corresponding zone goes
into alarm. It will remain flashing until it is
Acknowledged at which time it will go steady and
remain on until the alarm is reset. If the zone is
programmed as a time delay type, a steady LED
indicates the "pre-alarm" condition. If the zone is
isolated and in alarm it will also be steady.
Yellow
This LED illuminates if it's corresponding zone goes
into fault. It will remain on until the fault is removed.
Yellow
This LED illuminates if its corresponding zone is
isolated. It will remain on until the zone is de-
isolated.
IFS-2600 Installation & Programming Manual
Function
Buzzer
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes