Ceiling Suspended Type - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

SiUS30-604

Ceiling Suspended Type

Model
1 Cooling Capacity
2 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows×Stages×FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
4 Sound Level (H)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
Notes:
Specifications
FXHQ12MVJU
Btu/h
12,000
Btu/h
13,500
White (10Y9/0.5)
in
7-11/16×37-13/16×26-3/4
2×12×15
ft²
1.96
3D12K1AA1
Sirocco Fan
W
CFM
410/340
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Glass Wool
Resin Net (with Mold Resistant)
φ
in
1/4 (Flare Connection)
φ
in
1/2 (Flare Connection)
VP20
in
(External Dia. 1, Internal Dia. 3/4)
Lbs
dBA
Fuse Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping: 25ft (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation, these values are normally somewhat
higher as a result of ambient conditions.
FXHQ24MVJU
White (10Y9/0.5)
7-11/16×55-1/8×26-3/4
62
Microprocessor Thermostat
for Cooling and Heating
Resin Net (with Mold Resistant)
φ
3/8 (Flare Connection)
φ
5/8 (Flare Connection)
(External Dia. 1, Internal Dia. 3/4)
55
42
Fuse Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
24,000
27,000
3×12×15
3.15
3D12K2AA1
Sirocco Fan
130
710/600
Direct Drive
Microprocessor Thermostat
Glass Wool
Resin Net (with Mold Resistant)
VP20
(External Dia. 1, Internal Dia. 3/4)
80
44
Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
C:4D049326
Specifications
FXHQ36MVJU
36,000
40,000
White (10Y9/0.5)
7-11/16×62-5/8×26-3/4
2×12×15+2×10×15
3.66+2.95

Sirocco Fan
130
830/670
Direct Drive
for Cooling and Heating
Glass Wool
φ
3/8 (Flare Connection)
φ
5/8 (Flare Connection)
VP20
90
46
Fuse
R-410A Series
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents