P4" Outside Unit: Malfunction Of Inverter Radiating Fin; Temperature Sensor - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

SiUS30-604
2.35 "P4" Outside Unit:

Temperature Sensor

P4
Remote
Controller
Display
Applicable
RWEYQ60, 72, 84MTJU
Models
Method of
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Detection
Malfunction
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
Malfunction of Inverter Radiating Fin
Malfunction is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Defect of radiator fin temperature sensor
Defect of inverter PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Measure the resistance of
radiation fin thermistor.
Is the
resistance of thermistor
correct?
YES
Is the resetting possible?
YES
2: Refer to thermistor resistance / temperature characteristics table on P278.
Troubleshooting by Indication on the Remote Controller
NO
NO
Replace inverter PC board.
(Thermistor can not be removed
from inverter PC board)
Replace inverter PC board.
After resetting, restart.
(V2818)
205