A9" Indoor Unit: Malfunction Of Moving Part Of; Electronic Expansion Valve (Y1E) - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
"A9" Indoor Unit:
2.6
Expansion Valve (Y1E)
A9
Remote
Controller
Display
Applicable
All indoor unit models
Models
Method of
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Detection
Malfunction
When number of turns can't be detected even when output voltage to the fan is maximum
Decision
Conditions
Supposed
Causes
Troubleshooting
164
Malfunction of Moving Part of Electronic
Malfunction of moving part of electronic expansion valve
Defect of indoor unit PC board
Defect of connecting cable
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
The
electronic
expansion valve is
connected to X7A of the
indoor unit PC
board.
YES
Normal
when coil check
(∗1) of the moving part of
the electronic expansion
valve is
checked.
YES
The connecting
cable is short-circuited or
disconnected.
NO
NO
NO
YES
SiUS30-604
After connecting, turn the power
supply off and then back on.
Replace the moving part of the
electronic expansion valve.
Replace the connecting cable.
If you turn the power supply off
and turn on again, and it still does
not help, replace the indoor unit
PC board.
Troubleshooting
(V2781)