Daikin VRV - WII Service Manual page 138

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

SiUS30-604
3.2.4 Setting of Demand Operation
In order to save the power consumption, the capacity of outside unit is saved with control forcibly by
using "Demand 1 Setting" or "Demand 2 Setting".
To operate the unit with this mode, additional setting of "Normal Demand Setting" or external input
by external control adapter is required.
[Demand 1 setting]
Demand 1 setting 1
Demand 1 setting 2 (factory setting)
Demand 1 setting 3
[Demand 2 setting]
Demand 2 setting 2 (factory setting)
Test Operation
Setting
Setting
Other protection control functions have precedence over the above operation.
Standard for upper limit of power consumption
Approx. 60%
Approx. 70%
Approx. 80%
Standard for upper limit of power consumption
Approx. 40%
Field Setting
125