L4" Outside Unit: Malfunction Of Inverter Radiating Fin; Temperature Rise (R1T) - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
2.29 "L4" Outside Unit:

Temperature Rise (R1T)

L4
Remote
Controller
Display
Applicable
RWEYQ60, 72, 84MTJU
Models
Method of
Fin temperature is detected by the thermistor of the radiation fin.
Malfunction
Detection
Malfunction
When the temperature of the inverter radiation fin increases above 98°C.
Decision
Conditions
Supposed
Causes
Troubleshooting
196
Malfunction of Inverter Radiating Fin
Actuation of fin thermal (Actuates above 98°C)
Defect of inverter PC board
Defect of fin thermistor
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Temperature
of the radiator fin rises.
Actuates at min.
208°F
NO
Resistance
check of the radiator fin
thermistor
Normal
Is reset possible?
YES
2: Refer to thermistor resistance / temperature characteristics table on P278.
YES
Abnormal
NO
SiUS30-604
Defect of power unit radiation.
• Intake port is clogged
• Radiator fin is dirty
• Outdoor temperature is high
Replace the thermistor.
Replace the inverter PC board
Reset and operate.
(V2811)