C9" Indoor Unit: Malfunction Of Thermistor (R1T) For Suction Air - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
2.11 "C9" Indoor Unit:
Suction Air
C9
Remote
Controller
Display
Applicable
AII indoor unit models
Models
Method of
Malfunction detection is carried out by temperature detected by suction air temperature thermistor.
Malfunction
Detection
Malfunction
When the suction air temperature thermistor becomes disconnected or shorted while the unit is
running.
Decision
Conditions
Supposed
Causes
Troubleshooting
170
Malfunction of Thermistor (R1T) for
Defect of indoor unit thermistor (R1T) for air inlet
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Connector
is connected to X13A or X19A
of the indoor unit PC
board.
YES
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the indoor
unit PC board.
(7.2kΩ~
112kΩ)
YES
2: Refer to thermistor resistance / temperature characteristics table on P278.
NO
NO
SiUS30-604
Connect the connector and turn on
again.
Replace the thermistor R1T.
Replace the indoor unit PC board.
(V2786)