Ceiling Suspended Type - Daikin VRV III-S RXYMQ36 48PVJU Service Manual

R-410a heat pump 60hz
Table of Contents

Advertisement

SiUS34-907

Ceiling Suspended Type

Model
1 Cooling Capacity
2 Heating Capacity
Casing / Color
Dimensions: (H×W×D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Fan
Motor Output
Airflow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipes
Machine Weight (Mass)
4 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable Outdoor Unit
Standard Accessories
Drawing No.
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB (27°CDB), 67°FWB (19.4°CWB)
Outdoor temperature: 95°FDB (35°CDB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB (21°CDB).
Outdoor temperature: 47°FDB (8.3°CDB), 43°FWB (6°FWB)
Equivalent ref. piping length: 25ft (7.5 m), (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Specifications
FXHQ12MVJU
Btu/h
12,000
Btu/h
13,500
White(10Y9/0.5)
7-11/16 × 37-13/16 × 26-3/4
in. (mm)
(195 x 960 x 679)
2×12×15
ft² (m²)
1.96 (0.6)
3D12K1AA1
Sirocco Fan
W
62
cfm
410/340
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Wool
φ1/4 (6.4) (Flare Connection)
in. (mm)
φ1/2 (12.7) (Flare Connection)
in. (mm)
VP20
in. (mm)
(
External Dia. 1 (25.4)
Internal Dia. 3/4 (19.1)
Lbs (kg)
55 (25)
dBA
42
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
FXHQ24MVJU
24,000
27,000
White(10Y9/0.5)
7-11/16 × 55-1/8 × 26-3/4
(195 x 1400 x 679)
3×12×15
3.15 (1.0)
3D12K2AA1
Sirocco Fan
130
710/600
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Wool
Resin Net (with Mold Resistant)
φ3/8 (9.5) (Flare Connection)
φ5/8 (15.8) (Flare Connection)
VP20
)
(
External Dia. 1 (25.4)
Internal Dia. 3/4 (19.1)
80 (36)
44
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
C:4D049326
Specifications
FXHQ36MVJU
36,000
40,000
White(10Y9/0.5)
7-11/16 × 62-5/8 × 26-3/4
(195 x 1591 x 679)
2×12×15+2×10×15
3.66 + 2.95 (1.1 + 0.9)
Sirocco Fan
130
830/670
Direct Drive
Microprocessor Thermostat for Cooling
and Heating
Glass Wool
φ3/8 (9.5) (Flare Connection)
φ5/8 (15.8)(Flare Connection)
VP20
)
(
External Dia. 1 (25.4)
Internal Dia. 3/4 (19.1)
90 (41)
46
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual,
Drain Hose, Paper Pattern for
Installation, Clamp Metal, Insulation for
Fitting, Clamps, Washers.
)
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

R-410aVrv iii-s rxymq36-48pvju

Table of Contents