Inverter And Control Pc Board; Lc" Outside Unit: Malfunction Of Transmission Between - Daikin VRV - WII Service Manual

Water cooled inverter series heat pump heat recovery-60hz r-410a
Hide thumbs Also See for VRV - WII:
Table of Contents

Advertisement

SiUS30-604
2.33 "LC" Outside Unit:

Inverter and Control PC Board

LC
Remote
Controller
Display
Applicable
RWEYQ60, 72, 84MTJU
Models
Method of
Check the communication state between inverter PC board and control PC board by micro-
computer.
Malfunction
Detection
Malfunction
When the correct communication is not conducted in certain period.
Decision
Conditions
Supposed
Causes
Troubleshooting
Malfunction of Transmission between
Malfunction of connection between the inverter PC board and outside unit control PC board
Defect of outside unit control PC board (transmission section)
Defect of inverter PC board
Defect of noise filter
External factor (Noise etc.)
Troubleshooting by Indication on the Remote Controller