3.36 "Lc" Outdoor Unit; Lc" Outdoor Unit: Malfunction Of Transmission Between Inverter And Control Pc Board - Daikin VRV III RXYQ5-54PY1 Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller

3.36 "LC" Outdoor Unit:

Inverter and Control PC Board
LC
Remote
Controller
Display
Applicable
RXYQ5P~54P
Models
Method of
Check the communication state between inverter PC board and control PC board by micro-
computer.
Malfunction
Detection
Malfunction
When the correct communication is not conducted in certain period.
Decision
Conditions
Supposed
Causes
268
Malfunction of Transmission Between
Malfunction of connection between the inverter PC board and outdoor control PC board
Defect of outdoor control PC board (transmission section)
Defect of inverter PC board
Defect of noise filter
Faulty fan inverter
Incorrect type of fan inverter
Faulty compressor
Faulty fan motor
Si34-601A
Troubleshooting