Additional Analog Input Settings
Input Range Settings – The parameters in the following table adjust the input charac-
teristics of the analog current input. When using the inputs to command the inverter
output frequency, these parameters adjust the starting and ending ranges for the current,
as well as the output frequency range. Related characteristic diagrams are located in
"Analog Input Settings" on page
Func.
Name /
Code
SRW Display
A101 [OI]–[L] input active
range start frequency
OI-EXS
0000.0Hz
A102 [OI]–[L] input active
range end frequency
OI-EXE
0000.0Hz
A103 [OI]–[L] input active
range start current
OI-EX%S
00000%
A104 [OI]–[L] input active
range end current
OI-EX%E
00100%
A105 [OI]–[L] input start
frequency enable
OI-LVL
0Hz
3–13.
"A" Function
Description
The output frequency corre-
sponding to the current input
range starting point.
Range is 0.00 to 400.0 Hz
The output frequency corre-
sponding to the current input
range ending point.
Range is 0.00 to 400.0 Hz
The starting point for the
current input range.
Range is 0. to 100.%
The ending point for the
current input range.
Range is 0. to 100.%
Two options:
00... Use A101 start value
01... Use 0Hz
SJ200 Inverter
Defaults
Run
Mode
–FEF
–FU
Edit
(EU)
(USA)
0.0
0.0
0.0
0.0
0.0
0.0
100.
100.
01
01
3–27
Units
Hz
Hz
%
%
—