Output Function Summary Table - Hitachi SJ200 Series Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ200 Series:
Table of Contents

Advertisement

Output Function Summary Table – This table shows all ten functions for the logical
outputs (terminals [11], [12]) at a glance. Detailed descriptions of these functions,
related parameters and settings, and example wiring diagrams are in
Output Terminals" on page
Option
Terminal
Function Name
Code
Symbol
00
RUN
Run Signal
01
FA1
Frequency Arrival
Type 1 – Constant
Speed
02
FA2
Frequency Arrival
Type 2 – Over-
frequency
03
OL
Overload Advance
Notice Signal
04
OD
Output Deviation for
PID Control
05
AL
Alarm Signal
06
Dc
Analog Input
Disconnect Detect
07
FBV
PID Second Stage
Output
08
NDc
Network Detection
Signal
4–34.

Output Function Summary Table

ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
ON
when output to motor is at the set frequency
OFF
when output to motor is OFF, or in any accelera-
tion or deceleration ramp
ON
when output to motor is at or above the set
frequency, even if in accel. or decel. ramps
OFF
when output to motor is OFF, or at a level below
the set frequency
ON
when output current is more than the set thresh-
old for the overload signal
OFF
when output current is less than the set threshold
for the overload signal
ON
when PID error is more than the set threshold for
the deviation signal
OFF
when PID error is less than the set threshold for
the deviation signal
ON
when an alarm signal has occurred and has not
been cleared
OFF
when no alarm has occurred since the last
clearing of alarm(s)
ON
when the [O] input value < B082 setting (signal
loss detected), or the [OI] input current < 4mA
OFF
when no signal loss is detected
ON
Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is less
than the Feedback Low Limit (C053)
OFF
Transitions to OFF the PID Feedback Value (PV)
exceeds the PID High Limit (C052), and transi-
tions to OFF when the inverter goes from Run
Mode to Stop Mode.
ON
when the communications watchdog timer
(period specified by C077) has timed out
OFF
when the communications watchdog timer is
satisfied by regular communications activity
SJ200 Inverter
"Using Intelligent
Description
3–47