Analog voltage input calibration error
Hide thumbs Also See for L200:

Advertisement

Hitachi America, Ltd.
SUBJECT:
AFFECTED
MODELS:
Certain models of L200 and SJ200 were inadvertently shipped with the 0 – 10
Volt Analog Input (terminal O – L) span parameter improperly calibrated.
The symptom is easily determined. The inverter will operate properly with a
frequency reference from keypad potentiometer, analog 4 – 20 mA input or F001
setting. However when the frequency reference is set to the O voltage input, the
inverter will act erratically at 0 V input, and may trip on overcurrent. The output
frequency will ramp up linearly from 0 V to approximately 0.2 V input with a
corresponding output frequency of 0 to the maximum (factory default is 60 Hz)
frequency. From input voltages from 0.2 V to 10.0 V, the inverter output will
remain pegged at the maximum frequency.
To correct this problem, first stop the inverter. Then follow these steps:
1. Press FUNC to enter the PROGRAM mode.
2. Using the UP / DN arrow keys, navigate to parameter
3. Press FUNC to view the contents, and press UP arrow key to change the
value to
4. Press STR to save the change. This will make the so-called "debug"
parameters accessible.
5. Using UP arrow key, navigate to parameter
6. Press FUNC to view contents. It most likely is
PGC - 2/2/05
ENGINEERING NOTE
ANALOG VOLTAGE INPUT CALIBRATION ERROR
L200 and SJ200 – MFG DATE 0501 & BEFORE
0 1
EN-050202-1
C091
.
C12 1
6 5 5 3
Page 1 of 2

Advertisement

loading

Summary of Contents for Hitachi L200

  • Page 1 EN-050202-1 Hitachi America, Ltd. ENGINEERING NOTE SUBJECT: ANALOG VOLTAGE INPUT CALIBRATION ERROR AFFECTED L200 and SJ200 – MFG DATE 0501 & BEFORE MODELS: Certain models of L200 and SJ200 were inadvertently shipped with the 0 – 10 Volt Analog Input (terminal O – L) span parameter improperly calibrated.