Wiring the flame control solenoid:
Connect the two leads from the flame control solenoid to
the orange leads from the receiver. See Figure 8.33.
REMOTE
RECEIVER
RED
ORANGE
JAM NUT
REGULATOR
TOWER
Figure 8.33 Remote Receiver / Control Solenoid
Install a manometer into the pressure tap. Plug the remote
receiver into the 110-120 VAC power supply.
Light the appliance as directed in Section 9 of this manual.
Set the manifold pressure on the gas valve by rotating the
flame control solenoid. Adjust until the reading on the
manometer is 3.5 in. W.C. for natural gas or 10 in. W.C.
for LP.
Tighten the jam nut to the face of the variable regulator
body. See Figure 33 Turn the main gas knob on the gas
valve OFF. Remove the manometer from the pressure tap
and screw the tap closed.
Follow the instructions from the remote control kit to
operate and program the remote control.
BLUE
PLUNGER
Heat & Glo • Paloma • 7031-220 Rev. P • 10/08
REMOTE RECEIVER
TRANSFORMER
3 VAC
PLUG
IN
BATTERY PACK
Figure 8.34 Remote Control IPI Wiring Diagram
IGNITION MODULE
INTERMITTENT
3 VAC
PILOT IGNITOR
I
S
ORANGE
GROUND TO
FIREPLACE CHASSIS
RED
RED JUMPER
RED
WIRE TO
BROWN
VALVE
PIGGYBACK
ON/OFF SWITCH
FLAME
CONTROL
SOLENOID
ORANGE
ORANGE
43