Trane Thermostats Installation And Operation Manual page 31

Standard and programmable versions
Hide thumbs Also See for Thermostats:
Table of Contents

Advertisement

Table 7.
No.
(1) These options only available on systems with fans.
(2) See
(3) S ee
BAS-SVX36C-EN
Installation Options for 3-Heat/2-Cool Non-Programmable Thermostat
Name
Default
01
System type
0
02
Changeover
0
valve
(1)
03
Fan control
0
04
Stage 1 heat
5
(2)
cycle rate
05
Stage 1
3
compressor cycle
(2)
rate
06
Manual/Auto
0
changeover
07
Temperature
0
indication/
resolution
08
Compressor
5
protection
09
Heat
90
temperature
range stop
10
Cool temperature
50
range stop
11
Power supply
0
frequency
(3)
12
Deadband
3
13
Stage 2 heat
9
(2)
cycle rate
14
Auxiliary heat
5
(2)
cycle rate
15
Emergency heat
5
(2)
cycle rate
16
Stage 2
3
compressor cycle
(2)
rate
17
Auxiliary heat
0
control
18
Restore factory
0
defaults
"Heat and Cool Cycling Rate," p.
"Deadband," p.
41. For auto or manual systems (see Option 01).
Opts.
Descriptions
0
1H/1C, conventional - 1st stage heat (W), 1st stage
compressor (Y)
1
1H/1C, heat pump without auxiliary heat - 1st stage compressor (Y),
changeover (O/B)
2
1H, conventional without fan - 1st stage heat (W)
3
1H, conventional with fan - 1st stage heat (W), fan (G)
4
1C, conventional - 1st stage compressor (Y)
5
2H/1C, heat pump with auxiliary heat - 1st stage compressor (Y), changeover
(O/B), auxiliary heat (Aux/E)
6
2H/1C, conventional - 1st & 2nd stage heat (W,W2), 1st stage compressor (Y)
7
1H/2C, conventional - 1st stage heat (W), 1st & 2nd stage compressor (Y, Y2)
8
2H/2C, heat pump without auxiliary heat - 1st & 2nd stage compressor (Y,
Y2), changeover (O/B)
9
3H/2C, heat pump with auxiliary heat - 1st & 2nd stage compressor (Y, Y2),
changeover (O/B), auxiliary heat (Aux/E)
0
O/B terminal energized in cooling
1
O/B terminal energized in heating
0
Gas or oil furnace, equipment controls fan for heating
1
Electric furnace, thermostat controls fan in heating
1-10
Cycles per hour for 1st stage conventional heat - only available on systems
with conventional heat
1-5
Cycles per hour for 1st stage compressor - only available on systems with cool
stages
0
Manual changeover (heat/cool/off) - manually changeover between heat,
cool, and off
1
Auto changeover (heat/cool/auto/off) - manually changeover between heat,
cool, and off, or select automatic changeover
2
Auto changeover only (auto) - no manual changeover
0
°F with 1 degree resolution
1
°F with 0.5 degree resolution
2
°C with 1 degree resolution
3
°C with 0.5 degree resolution
4
°C with 0.1 degree resolution
0-5
Minutes for compressor off time - only available on heat pump systems or
systems with cool stages - (Minutes specified here are added to the 5 min
base off time.)
40-90
Heating high temperature range stop in °F. (4.5-32°C)
50-99
Cooling low temperature range stop in °F. (10-37°C)
0
60 Hz
1
50 Hz
2
2°F (1.0°C)
3
3°F (1.5°C)
4
4°F (2.0°C)
5
5°F (2.5°C)
6
6°F (3.0°C)
7
7°F (3.5°C)
8
8°F (4.0°C)
9
9°F (4.5°C)
1-10
Cycles per hour for 2nd stage conventional heat - only available for
conventional systems with at least two stages conventional heat
1-10
Cycles per hour for auxiliary heat - only for heat pump systems with more
heat than cool stages
1-10
Cycles per hour for emergency heat - only for heat pump systems with more
heat than cool stages.
1-5
Cycles per hour for 2nd stage compressor - only for systems with two cool
stages
0
Comfort
1
Economy
0
No - do not reset
1
Yes - reset all installation configurations (all settings in this table) to default
settings, except System selection
41.
Configuration
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

X13511535-01X13511536-01X13511537-011h/1c3h/2c

Table of Contents