Trane Thermostats Installation And Operation Manual page 27

Standard and programmable versions
Hide thumbs Also See for Thermostats:
Table of Contents

Advertisement

5. Press
6. Use
7. Repeat
8. Do one of the following to exit configuration mode:
Table 6.
No.
0100
0110
0120
0121
0122
0125
0126
0127
0128
0129
0130
BAS-SVX36C-EN
,
, or
to scroll through the options, identified by their numbers, until you reach
the option you want to change:
scrolls to a lower-numbered option.
or
scrolls to a higher-numbered option.
or
to change the value of the option:
decreases the value.
increases the value.
Step 5
and
Step 6
Note: Values are saved in permanent memory after setting a value and moving to next
configuration parameter, and also when you exit configuration mode.
• Remove the thermostat cover, if necessary, and then press and immediately release the
configuration button.
• Do not press any buttons for 10 min.
• Press and hold
for 2 sec.
Installation Options for 3-Heat/2-Cool Programmable Thermostat
Name
Default
Temperature
0
indication/
resolution
Clock format
12
Year
09
Month
1
Day
1
Daylight savings
2
(1)
Spring month
03
Spring day
08
Fall month
11
Fall day
08
System selection
8
until you have made all necessary changes.
Opts.
Descriptions
0
°F, 1 degree resolution
1
°F, 0.5 degree resolution
2
°C, 1 degree resolution
3
°C with 0.5 degree resolution
4
°C with 0.1 degree resolution
12
12 hour clock
24
24 hour clock
09-99
2009 - 2099
1-12
Months of the year
1-31
Days of the month
0
Disabled
1
US (1987), changeover at 2:00am
2
US (2007), changeover at 2:00am
3
Europe, changeover at 1:00am
4
Manual, changeover at 2:00am
01-12
The month in which the Spring daylight savings change occurs
01-31
The day on which the Spring daylight savings change occurs
01-12
The month in which the Fall daylight savings change occurs
01-31
The day on which the Fall daylight savings change occurs
1
1H/1C (conv) 1st Stage Heat (W), 1st Stage Comp (Y), Fan (G)
2
1H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Fan (G)
3
1H (Conv) 1st Stage Heat (W), without fan
4
1H (Conv) 1st Stage Heat (W), Fan (G)
5
1C (Conv) 1st Stage Comp (Y), Fan (G)
6
2H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Auxiliary Heat (W1),
Fan (G)
7
2H/2C (Conv) 1st & 2nd Stage Heat (W,W2), 1st & 2nd Stage
Comp (Y,Y2), Fan (G)
8
2H/1C (Conv) 1st & 2nd Stage Heat (W,W2), 1st Stage Comp (Y), Fan (G)
9
1H/2C (Conv) 1st Stage Heat (W), 1st & 2nd Stage Comp (Y,Y2), Fan (G)
10
2H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Fan (G)
11
3H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Auxiliary
Heat (W1), Fan (G)
Configuration
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

X13511535-01X13511536-01X13511537-011h/1c3h/2c

Table of Contents