Installation and Operation Thermostats Standard and Programmable Versions SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
Page 2
Trademarks Trane and its logo are trademarks ofTrane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners. Warnings, Cautions, and Notices...
– Trane Clarksville part # BAYSTAT151A – Service parts #THT02772 Note: To identify the thermostat type, locate theTrane PLM # and theTrane PLM #/Trane Clarksville # on the thermostat circuit board. The information contained in this document applies to either one or two models or to all.
Introduction Product Features and Capabilities The table below shows the functional differences between the three thermostat models. Thermostat Function or Feature A liquid crystal display (LCD) with symbols for temperature, setpoints, and system operating modes. The programmable thermostat also has day of the week, time of day, and occupancy settings.
Introduction Dimensions Figure 1 Figure 2 provide dimensions for each type of thermostat.The two non-programmable thermostats have the same dimensions; the programmable thermostat has slightly different dimensions. Figure 1. Programmable Thermostat Dimensions 0.3 in. (8 mm) 1.08 in. (27.5 mm) 3.25 in.
Page 8
Introduction Figure 2. 1-Heat/1-Cool or 3-Heat/2-Cool (non-programmable) Thermostat Dimensions 0.3 in. (8 mm) 1.1 in. (28 mm) 3.07 in. (78 mm) Typ. Radius 0.08 in. (2 mm) 4.7 in. (119 mm) 3.4 in. (86 mm) Typ.P Radius 0.08 in. (2 mm) Note: Drawing not to scale.
Pre-Installation This section provides the following pre-installation information: • Location considerations • Height requirements • Mounting surfaces • Maximum wire length Location Considerations When selecting a location, avoid the following: • Areas of direct sunlight • Areas in the direct airstream of air diffusers •...
Pre-Installation Maximum Wire Lengths Thermostat to HVAC Equipment The thermostat may not function properly if the total resistance of any of the thermostat to HVAC equipment wires exceeds 2.5 ohms.To ensure that wire length does not cause excess resistance, refer to Table 1 and ensure that the wires from the thermostat to the HVAC equipment are not too long.
Installation This section provides installation instructions. Before you begin, read through the pre-installation information, beginning on 9, and also verify the following conditions are met: • A wire access hole is available at the thermostat location. • The wires are accessible through the hole. •...
To wire the thermostat: 1. Connect the wires to the terminal block(s) packaged in the box with the thermostat. (The programmable thermostat has two terminal blocks, the non-programmable thermostats have only one): • Remove approximately 1/4 inch (6 mm) of insulation from the wires.
Installation 2. Align the pins on the circuit board with the holes on the bottom of the terminal blocks and gently push the wired terminal blocks into place on the circuit board. See Figure Figure 5. Attaching the wired terminal blocks to the pins on the circuit board Programmable thermostat 3-Heat/2-Cool thermostat 1-Heat/1-Cool thermostat...
The following diagrams show all of the common wiring scenarios you are likely to encounter. 1-Heat/1-Cool Thermostat Table 3 and the diagrams that follow to correctly wire the thermostat for your system type. Table 3. System Type Options for 1H/1C Non-Programmable Thermostats Value for Option 01 See Diagram System Type 1-heat/1-cool, conventional...
Compressor 3-Heat/2-Cool Non-Programmable Thermostat Table 4 and the diagrams that follow to correctly wire the thermostat for your system type. Table 4. System Type Options for 3H/2C Non-Programmable Thermostats See Diagram System Type Value for Option 01 1-heat/1-cool, conventional Figure 11...
Zoning Panels Programmable Thermostat Table 5 and the diagrams that follow to correctly wire the thermostat for your system type. Table 5. System Type Options for Programmable Thermostats See Diagram System Type Value for Option 130 1-heat/1-cool, conventional Figure 21...
2. The firmware version appears for 1.5 seconds: • On the programmable thermostat, the firmware version shows in the HH:MM digits. • On the non-programmable thermostats, the digits are split between the top and bottom regions of the screen: the most significant digits are at the top.
1. Apply electrical power to the thermostat. 2. See the appropriate table for your thermostat type to determine the configuration options you need: • Table 6, p. 27 for 3-Heat/2-Cool programmable thermostats • Table 7, p. 31 for 3-Heat/2-Cool non-programmable thermostats •...
Page 27
Configuration 5. Press , or to scroll through the options, identified by their numbers, until you reach the option you want to change: scrolls to a lower-numbered option. scrolls to a higher-numbered option. 6. Use to change the value of the option: decreases the value.
Page 28
Configuration Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued) Name Default Opts. Descriptions 0140 Schedule options Non-programmable Programmable 0150 TOD/Economizer Unused output TOD energizes terminal A during occupied period, not during (terminal A) unoccupied period. Economizer energizes terminal A during a call for cool 0151 Heat fan System controls fan...
Page 29
Configuration Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued) Name Default Opts. Descriptions 0220 Heat pump None compressor 15° F (–9.5° C) lockout point 20° F (–6.5° C) 25° F (–4.0° C) 30° F (–1.0° C) 35° F (1.5° C) 40°...
Page 30
Configuration Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued) Name Default Opts. Descriptions 0233 Scheduling mode 1 day - Mo-Su share the same schedule day options 5+1+1 days - Mo-Fr share a schedule; Sa and Su each have an independent schedule 5+2 days - Mo-Fr share a schedule;...
Page 31
Configuration Table 7. Installation Options for 3-Heat/2-Cool Non-Programmable Thermostat Name Default Opts. Descriptions System type 1H/1C, conventional - 1st stage heat (W), 1st stage compressor (Y) 1H/1C, heat pump without auxiliary heat - 1st stage compressor (Y), changeover (O/B) 1H, conventional without fan - 1st stage heat (W) 1H, conventional with fan - 1st stage heat (W), fan (G) 1C, conventional - 1st stage compressor (Y) 2H/1C, heat pump with auxiliary heat - 1st stage compressor (Y), changeover...
Page 32
Configuration Table 8. Installation Options for 1-Heat/1-Cool Non-Programmable Thermostat Name Default Opts. Descriptions System type 1H/1C, conventional -1st stage heat (W), 1st stage compressor (Y) 1H/1C, heat pump - 1st stage compressor (Y), changeover (O/B) 1H, conventional, without fan - 1st stage heat (W) 1H, conventional with fan -1st stage heat (W), fan (G) 1C, conventional - 1st stage compressor (Y) Changeover...
Space unoccupied indicator. no programming/ Timed override indicator scheduling-related buttons appear. Space occupied indicator Button lock indicator Overview of Operation If configured properly, both programmable and non-programmable thermostats will control HVAC equipment to maintain room temperature automatically. BAS-SVX36C-EN...
Operation Non-Programmable Thermostats Non-programmable thermostats do not have timekeeping or scheduling capabilities.They will continue to maintain heating and/or cooling setpoints until an operator makes changes to the setup.Therefore, only the following tasks may be required performed: • Change the system mode.
5 sec to save and exit. Programmable Thermostats Programmable thermostats contain all of the functionality of the non-programmable thermostats, but they also keep track of the date, day of week, and time of day for scheduling purposes. Programming This section describes how to program the thermostat after it has been installed and configured.
Operation Scheduling The thermostat can be configured for two periods (day and night) or four periods (morning, day, evening, and night).The chosen number of periods are applied to each day of the week when you program the thermostat. Each period can have a unique start time, heat setpoint, cool setpoint, and fan setting.
Page 37
Operation Table 9. Weekly Operating Schedule Worksheet Heating Cooling Period Start time setpoint setpoint Fan Setting Four period Morning 6:00 am 70° F (21.0° C) 78° F (25.5° C) Auto default settings 8:00 am 62° F (16.5° C) 85° F (29.5° C) Auto Evening 6:00 pm...
Page 38
Operation To set the schedule: 1. Press > > > .The display shows only the following elements: Mo Tu We Th Fr Sa Su 2. Press Note: At this point the thermostat is in schedule change mode. It returns to normal operating mode if no buttons are pressed for 45 sec.To manually exit schedule change mode, press and hold for 2 sec.
Operation Day-to-Day Operation After a programmable thermostat is configured and the schedule is programmed, the thermostat automatically changes the setpoints and fan settings according to the schedule.However, there are some operator tasks that you may need or want to perform: •...
Operation Timed Override (TOV) Mode During normal operation, the thermostat controls the HVAC equipment according to the schedule that is programmed into it.To permanently change the temperature setpoint or fan setting, make the change in the programmed schedule (see “Scheduling, ” p. 36).
Operational and Programming Reference Information This section provides additional information that may be useful for understanding thermostat operation or programming. Deadband The thermostat automatically maintains a temperature deadband between the heating setpoint and the cooling setpoint whenever automatic changeover (heat-to-cool or cool-to-heat mode) is enabled.The temperature range of the deadband is 2–9 °F (1.0–4.5°C) and is specified in the installation configuration options (see “Configuration, ”...
Note: You can manually revert to default settings by setting the appropriate installation parameter (#300 for programmable thermostats or #18 for non-programmable thermostats) to a value of 1, and exiting configuration mode.
Troubleshooting This section describes troubleshooting for the thermostat. Error Codes An error code indicates that technical assistance may be required. Try cycling the power to the thermostat as a first method to clear the error. See Table 10 below and Table 12, p.
Page 44
Thermostat Non-Prog XH/XC X########-## Rev X BAYSTAT15#X button ####XXX thermostats configuration button The configuration wrench icon appears, along with the option number and value. 3. Press and hold the configuration button again for at least 3 sec, then release it.The thermostat goes into system test mode: •...
Page 45
Troubleshooting 5. Use to change the value of the option: decreases the value. increases the value. 6. Repeat Step 4 Step 5 until you have conducted all needed tests. 7. Change the value of the power up test (test number 8 for the 1-Heat/1-Cool thermostat; test number 11 for the 3-Heat/2-Cool or programmable thermostat) to 1 to run a power up test after you exit test mode.
1 = show temperature reading in Celsius This setting is deactivated when you scroll to the next setting for the 3H/2C and programmable thermostats, but it remains active when you scroll to the next setting for the 1H/1C thermostat. Major software version Show major software revision number.
• If it does not recover to normal operation, have it serviced or replaced by a qualified Trane supplier. Blank display • Check the power supply. • If the power supply is ok, have the thermostat serviced or replaced by a qualified Trane supplier. Erratic display • Check the power supply.