Minimum Free Area Required For Each Combustion Air Opening Of Duct To Outdoors; Carbon Monoxide Poisoning Hazard; Outdoor Combustion Air Method - Payne PG8MAA Installation And Operating Instructions Manual

Series 140/e single-stage deluxe, induced-combustion 4-way multipurpose gas furnace
Table of Contents

Advertisement

CARBON
MONOXIDE
POISONING
HAZARD
Failure
to follow
this warning
could
result
in personal
injury or death.
The
operation
of exhaust
fans,
kitchen
ventilation
fans,
clothes
dryers,
attic exhaust
fans or fireplaces
could
create a
NEGATIVE
PRESSURE
CONDITION
at the
furnace.
Make-up
air MUST
be provided
for the ventilation
devices,
in addition
to that required
by the furnace.
Refer to Carbon
Monoxide
Poisoning
Hazard
warning
in venting
section
of
these
instructions
to deternfine
if an adequate
amount
of
make-up
air is available.
The
requirements
for combustion
and ventilation
air depend
upon whether
or not the furnace
is located
in a space
having
a
volume
of at least 50 cu/ft, per 1,000 Btuh input rating for all gas
appliances
installed
in the space.
Spaces having
less than 50 cu/ft, per 1,000 Btuh re-
quire the OUTDOOR
COMBUSTION
AIR
METHOD.
Spaces having
at least 50 cu/fl, per 1,000 Btuh may use
the INDOOR
COMBUSTION
AIR, STANDARD
or
KNOWN
AIR INFILTRATION
METHOD.
Outdoor
Combustion
Air Method
1. Provide
the space
with sufficient
air for proper
combus-
tion, ventilation,
and dilution
of flue gases using perman-
ent horizontal
or vertical
duct(s)
or opening(s)
directly
communicating
with
the
outdoors
or spaces
that freely
communicate
with the outdoors.
2. Fig.
7
illustrates
how
to
provide
TWO
OUTDOOR
OPENINGS,
one
inlet
and
one
outlet
combustion
and
ventilation
air opening,
to the outdoors.
e. One opening
MUST
commence
within
12 in. (300
ram) of the ceiling
and the second
opening
MUST
commence
within
12 in. (300 ram) of the floor.
f. Size openings
and ducts per Fig. 7 and Table 2.
g. TWO HORIZONTAL
DUCTS
require
1 sq./in, of free
area per 2,000 Btuh (1,100
mm2/kW)
of combined
input for all gas appliances
in the space per Fig. 7 and
Table 2.
h. TWO OPENINGS
OR VERTICAL
DUCTS
require
1
sq./in, of free area per 4,000 Btuh (550 mm2/kW)
for
combined
input of all gas appliances
in the space per
Fig. 7 and Table 2.
3. ONE OUTDOOR
OPENING
requires:
a. 1 square inch of free area per 3,000 Btuh (734
mm2/kW)
for combined
input of all gas appliances
in
the space per Table 2 and
b. Not less than the sum of the areas of all vent connect-
ors in the space.
The opening
shall
commence
within
12 in. (300
ram)
of the
ceiling. Appliances
in the space shall have clearances
of at least 1
in. (25 ram) from the sides and back and 6 in. (150 ram) from the
front. The opening
shall directly
communicate
with the outdoors
or shall conmmnicate
through
a vertical
or horizontal
duct to the
outdoors
or spaces
(crawl or attic) that freely communicate
with
the outdoors.
Indoor
Combustion
Air NFPA & AGA
Standard
and Known-Air-Infiltration
Rate Methods
Indoor
air is pernfitted
for combustion,
ventilation,
and dilution,
if the Standard
or Known-Air-Infiltration
Method
is used.
CARBON
MONOXIDE
POISONING
HAZARD
Failure
to follow
this warning
could
result
in death
and/or
personal
iniury.
Many
homes
require
air to be supplied
from
outdoors
for
furnace
combustion,
ventilation,
and dilution
of flue gases.
The
furnace
combustion
air supply
must
be provided
in
accordance
with this instruction
manual.
Table 2--Minimum
Free Area Required
for Each
Combustion
Air Opening
of Duct to Outdoors
TWO
OPENINGS
OR VERTICAL
TWO
HORIZONTAL
DUCTS
SINGLE
DUCT
OR OPENING
DUCTS
FURNACE
(1 SQ. IN./2,000
BTUH)
(1 SQ. IN./3,000
BTUH)
(1 SQ. IN./4,000
BTUH)
INPUT
(1,100
SO. MMiKW)
(734
SO. MMiKW)
(550
SO. MMiKW)
(BTUH)
Free Area
of Open-
Round
Duct
Free Area
of Open-
Round
Duct
Free Area
of Open-
Round
Duct
ing and
Duct
Dia.
ing and
Duct
Dia.
ing and
Duct
Dia.
Sq. In. (Sq. ram)
In. (ram)
Sq. In. (Sq. ram)
In. (ram)
Sq. In. (Sq. ram)
In. (ram)
44,000
22
(14194)
6 (152)
14.7
(9484)
5 (127)
11
(7096)
4 (102)
66,000
33
(21290)
7 (178)
22.0
(14193)
6 (152)
16.5
(10645)
5 (127)
88,000
44
(28387)
8 (203)
29.3
(18903)
7 (178)
22
(14193)
6 (152)
110,000
55
(35484)
9 (229)
36.7
(23677)
7 (178)
27.5
(17742)
6 (152)
132,000
66
(42580)
10
(254)
44.0
(28387)
8 (203)
33
(21290)
7 (178)
154,000
77
(49677)
10
(254)
51.3
(33096)
9 (229)
38.5
(24839)
8 (203)
EXAMPLES:
Determining
Free Area
FURNACE
WATER HEATER
TOTAL INPUT
110,000
+
30,000
=
(140,000 divided by 4,000)
=
35.0 Sq. In. for each two Vertical Ducts or Openings
66,000
+
40,000
=
(106,000 divided by 3,000)
35.3 Sq. In. for a Single Duct or Opening
88,000
+
30,000
=
(118,000 divided by 2,000)
59.0 Sq. In. for each of two Horizontal
Ducts

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pg8jaa

Table of Contents