220V Operation

If the machine is not wired correctly a fire
could result. Make sure your wiring, recep-
tacle, plug, and circuit breaker can handle
the current draw of the machine. If you are
not sure that your electrical circuit can han-
dle the current draw, get a qualified electri-
cian to test your electrical system and do
any required upgrades. Do not attempt to
modify an existing circuit by only replacing
the circuit breaker with one rated for a high-
er amperage draw than the wiring, recepta-
cle, and plug are rated for.
The motors supplied with the Models ZFX, PROZ,
& PROZX are prewired to operate at 220V.
Models ZFX, PROZ, & PROZX:
Under normal 220V use, the motor draws approx-
imately 13 amps. Use a 15 amp circuit breaker or
a 15 amp slow-blow fuse for 220V operation.
-10-
The Models ZFX, PROZ, & PROZX do not come
with a plug. When operating at 220V, use a
NEMA-style 6-15 plug and receptacle as shown in
Figure 6.
Figure 6. NEMA-style 6-15 plug and receptacle.
The circuit you use should be dedicated, (i.e., the
machine should provide the only draw from that
circuit). If frequent circuit failures occur when
using
this
machine,
Department or your local electrical contractor.
contact
our
Service