Using Features and Options
6.6 Relay Interface Module
An optional RIM uses relay contact closures to indicate the operating status and alarm
condition of the UPS system. A maximum of two monitoring accessories (RMPs, RIMs, or
SCMs) can be installed. See Table 6-1 on page 6−4 for the number of accessories
permitted. Figure 6-4 shows the RIM with its four 15-pin connectors labeled J1 through J4.
The RIM can provide the following signals:
UPS AVAILABLE
UPS OFF LINE
BATTERY WEAK
UTILITY FAILURE
6−6
EATON Powerware
Figure 6-4. Relay Interface Module
Pins 1 and 12
Contacts are closed when the UPS is offline.
Pins 3 and 13
Contacts are closed when the UPS is operating in
Normal mode.
Pins 5 and 14
Contacts are closed when approximately two
minutes of battery time is remaining, before the
critical load is lost.
Pins 6 and 15
Contacts are closed when Utility Failure is detected.
9315 UPS (300–500 kVA) Operation Manual S 164201119 Rev F www.powerware.com
®